Critical Power from GE
Overview
The GE Innity S DC energy system is
a compact power plant that supports
dual voltage (+24V/-48V) operation
through the use of a comprehensive
range of advanced rectiers and
DC-DC converters. Primary voltage
is supported by rectiers and battery
reserve, while secondary voltage is
supported by DC-DC converter modules.
Primary voltage can be -48V or +24V.
The Innity S Power System has primary
voltage capacity for +24V power up to
1,200A and -48V power up to 800A.
Secondary voltage capacity is up to 120A
(48V out) and 300A (24V out).
Shelf / Bay Options
Innity S systems features mounting
rails for eld install applications and may
be equipped in a 7 ft 23” relay rack; or a
half height rack for mounting on battery
stands. The distribution module is 4U
tall and accommodates up to 26 single
voltage or selectable voltage bullet
breaker positions. Universal shelves
are 1U tall with four slots that accept
any Innity series rectier or converter
interchangeably in any power slot. This
allows the available slots to be lled
with the mix of power modules desired.
The only restriction is whether AC
power is applied to the shelf. This gives
extreme exibility in the provisioning
of power modules within the system.
Innity Rectier and
Converter Family
The Innity Series oers DC rectiers
and converters for both +24V to -48V
and -48V to +24V applications. For
easy module selection, the rectiers
and converters are color coded to
quickly identify voltage, module type
and input voltage type (AC or DC).
Galaxy Pulsar*
Plus Controller
The Galaxy Pulsar Plus is used
throughout many of the GE DC Power
products including Innity, CP, and SPS
with the only dierentiator being the
form factor which is scaled to meet the
nature of the application. The controller
utilizes standard network management
protocols allowing for advanced
network supervision with SNMP
communications to deliver extensive
monitoring and control features with
both local and remote access.
Advantages
Dual Voltage power system
with ultimate flexibility
-48V up to 800A or
+24V up to 1200A
Secondary voltage
up to 300A
High availability wireless
telecom applications
Telecom service providers
Efficiency
approaching 97%
Innity S Power System
Compact, Dual Voltage,
Rack Mounted Power System
2
Innity S Ordering Guide | www.gecriticalpower.com
Innity Rectiers and Converters
Compact – 1RU form factor providing high power density (24 W/in
3
)
Dual Voltage compatibility – the unique connector pin designation allows the
rectifier to be used in a “universal” power shelf, alongside rectifiers or DC-DC
converters with different output voltages.
Plug and Play – installation of the rectifier in a shelf connected to a compatible
system controller initializes all set up parameters automatically. No adjustments
are needed.
Extended service life – parallel operation with automatic load sharing ensures that
parallel units are not unduly stressed even when a unit fails or is removed.
Monitoring / control – the built in microprocessor controls and monitors all critical rectifier functions and communicates with
the system controller using the built in Galaxy Protocol serial interface.
Fail safe performance – hot insertion capabilities allow for converter replacement without system shutdown; soft start and
inrush current protection prevent nuisance tripping of upstream breakers.
Applications
Key Features
Specications
Telecommunications Networks
Digital Subscriber Line (DSL)
Indoor/Outdoor Wireless
Routers/Switches
Fiber in the Loop
Transmission
Data Networks
Distributed Antenna Systems
Off-Grid/On-Grid Renewable
Energy Sites
Extended Temperature Range
Redundant Fan Cooling
Front Panel LED Indicators
1U Height, Hi Power Density
277/220/110V AC Input
Digital Load Sharing
Hot Pluggable
RoHS compliant
Direct Solar Input
(no inverter required)
INPUT NE100AC24ATEZ
NE100ECO24ATEZ
NE050AC48ATEZ
NE050ECO48ATEZ
NE075AC48ATEZ NE030DC48A NE040DC48A NE075DC24A
Voltage Range 95-305Vac 95-305Vac 95-305Vac 21-30Vdc 21-30Vdc 42-60Vdc
Input Current 15-12A @ 100-120Vac
15-12A @ 200-277Vac
15-12A @ 100-120Vac
15-12A @ 200-277Vac
15-12A @ 100-120Vac
22-15.5A @ 200-277Vac
63A @ 27Vdc
81A @ 21Vdc
94A @ 27Vdc
108A @ 21Vdc
41A @ 54.5Vdc
54A @ 42Vdc
Input
Frequency
45 – 66Hz 45 – 66Hz 45 - 66Hz - - -
Power Factor 0.98 at>50% load 0.98 at>50% load 0.98 at>50% load - - -
Eciency > 95% (Peak 95.6%) > 96% (Peak 96.9%) > 96% (Peak 96.9%) - - -
Total Harmonic
Distortion
<5% @loads over 50% <5% @loads over 50% <5% @loads over 50% - - -
3
Innity S Ordering Guide | www.gecriticalpower.com
Specications (Cont.)
OUTPUT NE100AC24ATEZ
NE100ECO24ATEZ
NE050AC48ATEZ
NE050ECO48ATEZ
NE075AC48ATEZ NE030DC48A NE040DC48A NE075DC24A
Voltage Adjust
RAnge
21-29Vdc 42-58Vdc 42-58Vdc
46-57Vdc
46-57Vdc 23-28Vdc
Voltage Nominal 27.25V 54.5V 54.5V 52.0V 52.0V 27.2V
Regulation
(with controller)
±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
Ripple 100mVrms 100mVrms 100mVrms 100mVrms 100mVrms 100mVrms
Output Current
- High-Line
- Low-Line
114A @24V
100A @27.25V
44A @27.25V
57A @48V
50A @54.5V
22A @54.5V
82A@48V
75A @54.5V
22A @54.5V
30A @52.0V
-
-
-
40A @52.0V
-
-
-
75A @27.2V
-
-
-
Heat Dissipation
@ max out
1
174W / 594 BTU/hr 158W / 539 BTU/hr 249W / 850 BTU/hr
154W / 525
BTU /hr
205W / 700
BTU/ hr
202W / 689
BTU/hr
1
Special room cooling may be required.
OUTLINE DRAWING
ENVIRONMENTAL
Operating Temperature -40°C to +75°C (-40°F to 167°F) Full capacity up to 55°C; output derates 2%/°C from 55°C to 75°C
Storage Temperature -40°C to +85°C (-40°F to 185°F)
Humidity < 95% non-condensing
Altitude 4000M (for altitudes above 2000M, peak operating temperature de-rates 0.656º C /100M;
4000M peak temperature rating is 62ºC
SAFETY AND STANDARDS COMPLIANCE
NEBs Level 3 Evaluated by independent NRTL test lab to Telcordia GR63-CORE and GR1089-CORE Issue 6 [Level 3]
Safety ANSI/UL60950-1-2014 and CAN/CSA C22.2 No. 60950-1-07, Second Edition + A2:2014 (MOD), dated October 14, 2014
RoHS Compliant to RoHS EU Directive 2002/95/EC; RoHS 6/6 models with Z sux (RoHS 5/6 all other models)
EMC European Directive 2014/30/EU; EN55032, Class A; EN55035; FCC, Class A; GR1089-CORE
ESD EN61000-4-2, Level 4
MECHANICAL
Length (inch/mm) 13.85 / 351.8
Width (inch/mm) 5.23 / 133
Height (inch/mm) 1.63 / 42
Weight (lb/Kg) 5.05 / 2.2
4
Innity S Ordering Guide | www.gecriticalpower.com
Pulsar Plus Controller
Applications
The Pulsar Plus family of controllers provides system monitoring and control features
for Innity, CP, and other power systems. These controllers monitor and control
system components including rectiers, converters, and distribution modules via a
multi-drop RS485 digital communications bus. System status, parameters, settings,
and alarm thresholds can be viewed and congured from the controller’s front panel
display. Assignment and conguration of alarm inputs and output relays can be
performed from a laptop computer connected to a local RS-232 or Ethernet port, or by remote access is through a secure network
connection to the World Wide Web (internet) or your enterprise network (intranet). An optional modem is also available.
This controller utilizes standard network management protocols allowing for advanced network supervision. The GE Galaxy Manager*
software is the centralized visibility and control component of a comprehensive power management system designed to meet
engineering, operations and maintenance needs. The Galaxy Manager client-server architecture enables remote access to system
controllers across the power network, featuring ECO Priority advanced monitoring features which provides detailed energy source
analysis to help better customize your renewable energy resources.
Telecommunications Networks
Digital Subscriber Line (DSL)
Indoor/Outdoor Wireless
Routers/Switches
Fiber in the Loop
Transmission
Off-Grid/On-Grid Renewable
Energy Sites
Data Networks
PBX
Remote Access and Features
Integrated 10/100Base-T
Ethernet Network
- TCP/IP with IPV6 Capability
- SNMP V3 for management
- SMTP for email
- Telnet for command line interface
- DHCP for plug-n-play
- FTPS for rapid backup and upgrades
- HTTPS for standard web pages
and browsers
- Compatible with Galaxy Manager
and other management packages
- Shielded RJ-45 interface
referenced to chassis ground
Password protected security levels:
User, Super-User, Administrator
for all access
Ground-referenced RS232 system port
ANSI T1.317 command-line interface
Modem access support
- Remote via external modem
- Callback security
EasyView2, Windows-based GUI
software for local terminal or
Modem access
ECO Priority controls and features
- Advanced generator controls to
help minimize fuel consumption
for off grid applications
- ECO Energy Management allowing
for non-ECO sources outputs to be
minimized while ECO resources
are available
- Source and load trend logging
Standard System Features
Monitor and control of more than 40
connected devices
- Robust RS485 system bus
Standard and user defined alarms
- Alarm test
- Assignable alarm severity:
Critical, Major, Minor, Warning,
and record- only
- 10 alarm relays (7 user assigned)
Rectifier management features
- Automatic rectifier restart
- Active Rectifier Management
ARM (energy efficiency)
- Remote rectifier (on/off)
- Reserve Operation
- Automatic rectifier sequence control
- N + X redundancy check
Multiple Low Voltage Load and Low
Voltage Battery Disconnect thresholds
Configuration, statistics, and history
- All stored in non-volatile memory
- Remote/local backup and restore
of configuration data
Industry standard defaults
- Customer specific
configurations available
Remote/local software upgrade
Basic, busy hour, and trend statistics
Detailed event history
User defined events and
derived channels
Standard Battery Management Features
Float/boost mode control
- Manual boost
- Manual timed boost locally, T1.317,
and remotely initiated
- Auto boost terminated by time
or current
Battery discharge testing
- Manual (local/remote)
- Periodic
- Plant Battery Test (PBT)
input driven
Key Features
5
Innity S Ordering Guide | www.gecriticalpower.com
Key Features (Cont.)
- Configurable threshold or
20% algorithm
- Graphical discharge data
- Rectifiers on-line during test
Slope thermal compensation
- High temperature
- Low temperature
- Step temperature
- STC Enable/Disable,
low temperature Enable/Disable
- Configurable mV/°C slopes
State of charge indication
High temperature disconnect setting
Reserve-time prediction
Recharge current limit
Emergency Power-Off input
Integrated Monitoring Inputs/Outputs
System plant voltage (accuracy ±0.5%, resolution 0.01V)
One system shunt (accuracy ±0.5% full scale, resolution 1A)
- Battery or load
- Mounted in the return side of DC bus
Up to 15 binary inputs
- 6 inputs close/open to battery
- 9 input close/open to return
- User assignable
Up to 7 Form-C output alarms (60VDC @ .5A)
- User assignable
1-Wire™ bus devices
- Up to 16 temperature probes (QS873)
- Up to 6 mid-string monitors (ES771)
Galaxy Manager Compatible
Centralized web server and database with multiple
user access to live or managed data with drill down
to problem details
Monitor and control of more than 40 connected devices
Management information from polling or alarms received
from alarm traps from multiple sites are available on one
screen via the inter/intranet
Trend user selected data over time
Automatic or manual report generation
Standard engineering tools like reserve time calculators
and cable voltage drop analyzer
GENERAL
Operating Voltage ±24 Vdc, ±48 Vdc
(Range: ±18 to ±60 Vdc)
No Alarms Menu 1
No Alarms Menu 1
No Alarms Menu 1
Input Power Less than 7W
Operating Temperature Range -40°C to +75°C (-40°F to 167°F)
Operating Relative Humidity 0 - 95% (non-condensing)
Storage Temperature Range -40°C to +85°C (-40°F to 185°F)
Physical Specications Sizes vary by packaging option
Display 8-line by 40-character with alarm context
sensitive backlit LCD
SAFETY AND STANDARDS COMPLIANCE
NEBs Evaluated by independent NRTL test lab to Telcordia GR63, Issue 3 and GR1089-CORE, Issue 6
Safety ANSI/UL60950-1-2014 and CAN/CSA C22.2 No. 60950-1-07, Second Edition + A2:2014 (MOD), dated October 14, 2014
RoHS Compliant to RoHS EU Directive 2002/95/EC RoHS 6/6
EMC European Directive 2014/30/EU; EN55032, Class A, EN55035; FCC, Class A; GR1089-CORE, Issue 6
AGENCY CERTIFICATIONS
NEBs Level 3 Evaluated by independent NRTL test lab to Telcordia GR63, Issue 3 and GR1089-CORE, Issue 6
EMC European Directive 2014/30/EU; EN55032, (CISPR22) Class A, EN55035 (CISPR24)
Safety Underwriters Laboratories (UL) Listed per Subject Letter 1801: Power Distribution Center for (CSA 22.2 950):
Safety of Information Technology Equipment
Specifications
6
Innity S Ordering Guide | www.gecriticalpower.com
Pulsar Edge Controller
Applications
Telecommunications Networks
Digital Subscriber Line (DSL)
Indoor/Outdoor Wireless
Routers/Switches
Fiber in the Loop
Transmission
Data Networks
PBX
The SPS Pulsar Edge controller delivers large system intelligence in a small system form
factor. This family of controllers functionsas network interface cards (NIC) and as a full-
featured battery plant controller. Its thin modular plug-in form factor minimizes shelf
space consumption allowing maximum power module and distribution capabilities.
The controller is utilized in bulk power applications in data centers and enterprise
applications. Ethernet connectivity with SNMP V3 facilitates secure remote network
management. Access through its front-accessible RS232 or USB port and aided by the EasyView2 graphical enables full user
interface locally. Optional 1U display version allows convenient access to all controller functions without requiring external cable
connections. The display also features alarm context sensitive backlighting for at-a-glance system status.
As a battery plant controller, it provides a complete set of features to monitor and control rectiers, batteries, and distribution. A
exible set of congurable inputs allow the Pulsar Edge controller to monitor a wide variety of system equipment and incorporate
appropriate state information enabling a centralized point of management . The controller utilizes standard network management
protocols allowing for advanced network supervision. GE Galaxy Manager* software is the centralized visibility and control
component of a comprehensive power management system designed to meet engineering, operations and maintenance needs.
The Galaxy Manager client-server architecture enables remote access to system controllers across the power network.
Key Features
Remote Access and Features
Integrated 10/100Base-T Ethernet
Network
- TCP/IP with IPV6 Support
- SNMP V3 for management
- SMTP for email
- Telnet for command line interface
- DHCP for plug-n-play
- FTPS for rapid backup and upgrades
- HTTPS for standard web pages
and browsers
- Compatible with Galaxy Manager
and other management packages
- Shielded RJ-45 interface
referenced to chassis ground
Password protected security
levels: User, Super-User,
Administrator for all access
Ground-referenced
RS232 system port
ANSI T1.317 command-line interface
Modem access support
- Remote via external modem
- Callback security
EasyView2, Windows-
based GUI software for local
terminal or Modem access
Optional 1U display with alarm
indicating backlight feature
Standard System Features
Monitor and control of more than 40
connected devices
- Maximum of 32 rectifiers
- Maximum of 6 distribution
control cards
- Robust RS485 system bus
Standard and user defined alarms
- Alarm test
- Assignable alarm severity:
Critical, Major, Minor,
Warning, and record-only
Rectifier management features
- Automatic rectifier restart
- Adaptive Rectifier Management
(energy eff iciency)
- Remote rectifier (on/off)
- Reserve Operation
- Automatic rectifier
sequence control
- N + X redundancy check
Multiple Low Voltage Load
and Low Voltage Battery
Disconnect thresholds (4)
Configuration, statistics, and history
- All stored in non-volatile memory
- Remote/local backup and
restore of configuration data
Industry standard defaults
- Customer specific
configurations available
Remote/ local software upgrade
Basic, busy hour, and trend statistics
Detailed event history
User defined events and
derived channels
7
Innity S Ordering Guide | www.gecriticalpower.com
Key Features (Cont.)
Standard Battery Management Features
Float/boost mode control
- Manual boost
- Manual timed boost locally, T1.317,
and remotely initiated
- Auto boost terminated
by time or current
Battery discharge testing
- Manual (local/remote)
- Periodic
- Plant Battery Test (PBT) input driven
- Configurable threshold or
20% algorithm
- Graphical discharge data
- Rectifiers on-line during test
Slope thermal compensation
- High temperature
- Low temperature
- Step temperature
- STC Enable/Disable, low temperature
Enable/Disable
- Configurable mV/°C slopes
State of charge indication
High temperature disconnect setting
Reserve-time prediction
Recharge current limit
Emergency Power-Off input
GENERAL
Operating Voltage ±24 Vdc, ±48 Vdc (Range: ±18 to ±60 Vdc)
Input Power Less than 7W
Operating Temperature Range -40°C to +70°C (-40°F to 167°F)
Operating Relative Humidity 0 - 95% (non-condensing)
Storage Temperature Range -40°C to +85°C (-40°F to 185°F)
Physical Specications 1.75 in. H, 0.75 in. W, 8.00 in. D; 0.5lb
Display 8-line by 40-character backlit LCD
EMC FCC/EN55032 Class A, CISPR22 Level A
AGENCY CERTIFICATIONS
Electrostatic Discharge EN 61000-4-2 level 4
Radiated Emissions FCC, Class A; EN 55032, Class A
Safety UL listed Component as Part of CPL or SPS Power System; ANSI/UL60950-1-2014 and CAN/CSA C22.2 No. 60950-1-07,
Second Edition + A2:2014 (MOD), dated October 14, 2014
Integrated Monitoring Inputs/Outputs
System plant voltage (accuracy ±0.5%, resolution 0.01V)
One system shunt (accuracy ±1% full scale, resolution 1A)
- Battery or load
- Mounted in the return side of DC bus
Up to 15 binary inputs
- 6 inputs close/open to battery
- 9 input close/open to return (number is dependent upon
number of output alarms)
- User assignable
Up to 6 user assignable Form-C output alarms (50VDC @.3A)
1-Wire™ bus devices
- Up to 16 temperature probes (QS873)
- Up to 6 mid-string monitors (ES771)
Galaxy Manager Compatible
Centralized web server and database with multiple
user access to live or managed data with drill down
to problem details
Monitor and control of more than 40 connected devices
Management information from polling or alarms received
from alarm traps from multiple sites are available on one
screen via the inter/intranet
Trend user selected data over time
Automatic or manual report generation
Standard engineering tools like reserve time calculators
and cable voltage drop analyzer
Specifications
8
Innity S Ordering Guide | www.gecriticalpower.com
Innity S System
Applications
Key Features
Specications
Innity S may be congured as a +24V or -48V single voltage power system or as a dual
voltage power system that supports rectiers and converters. The primary voltage is
supported by +24V or -48V rectiers and battery reserve, while secondary voltage is
supported by DC-DC converters. Innity-S includes dedicated 24V, 48V and return
buses. The primary voltage capacity is 1,200A at 24V and 800A at 48V. Secondary
(-48V) voltage capacity is up to 120A, (24V) voltage capacity is up to 300A. The system
includes low voltage battery disconnect option for the primary voltage. A low voltage
load disconnect option can be used for load shedding to maintain critical loads.
Wireless Telecom Networks
Indoor/Outdoor Wireless
Transmission
Data Networks
Off-Grid/On-Grid
Renewable Energy Sites
Dual Voltage Flexibility
Redundant Fan Cooling
Front Panel LED Indicators
1U Height, Hi Power Density
220/110 V AC Input
Digital Load Sharing
Hot Pluggable
RoHS Compliant
ECO Priority Ready
PRIMARY OUTPUT
Nominal Voltage 24Vdc -48Vdc
Output Current 1,200A 800A
Vo Setpoint (factory) 27.2Vdc±1% -54.5Vdc±1%
Vo Range +21Vdc to +29Vdc -42Vdc to -58Vdc
Regulation ±0.5%
INPUT MIN TYP MAX
Voltage Range
- High-Line
- Low-Line
175Vac
85Vac
220Vac
110Vac
305Vac
140Vac
Frequency 45Hz 60Hz 66Hz
Power Factor 98% 99.5%
Total Harmonic Distortion 5%
SECONDARY OUTPUT
Nominal Voltage -48Vdc +24Vdc
Output Current 120A 300A
Vo Setpoint (factory) -54.5Vdc±1% 27.25Vdc±1%
Vo Range -42Vdc to -58Vdc +21Vdc to +29Vdc
Regulation ±0.5%
9
Innity S Ordering Guide | www.gecriticalpower.com
MECHANICAL SYSTEM ONLY FRAME MOUNTED SYSTEM
Height (in. /mm) 21.25 / 540 (Base system with 4 power shelves and 2 distributions) 84 / 2134
Width (in. /mm) 19 / 482.6 or 23 / 584.2 23 / 584.2 or 26 / 660.4
Depth (in. /mm) 21 / 533 21 / 533
Weight (lb / Kg) 108 / 49 (Base system with 4 power shelves and 2 distributions)
292 / 132.5 (Base system in 23” Frame with 4 power shelves and
2 distributions)
292 / 132
ENVIRONMENTAL
Operating Temperature -40°C to +75°C (-40°F to 167 °F)
Storage Temperature -40°C to +85°C (-40°F to 185 °F)
Relative Humidity 95% max, non-condensing
Altitude 4000M (for altitudes above 2000M, peak operating temperature de-rates 0.656º C /100M; 4000M peak temperature rating is 62º C
OUTLINE DRAWING (FOR VISUAL REFERENCE ONLY)
Specications (Cont.)
AGENCY CERTIFICATIONS
CSA ANSI/UL60950-1-2014 and CAN/CSA C22.2 No. 60950-1-07, Second Edition + A2:2014 (MOD), dated October 14, 2014
EMI/EMC European Directive 2014/30/EU; EN55032 (CISPR22) Class A; EN55035 (CISPR24)
NEBS LEVEL 3 GR1089-CORE
Special equipment room cooling may be needed - heat dissipation exceeds values of GR-63 Table 4-5
SAFETY AND STANDARDS COMPLIANCE
NEBs Evaluated by independent NRTL test lab to Telcordia GR63-CORE and GR1089-CORE [Level 3] ISSUE 6
Safety ANSI/UL60950-1-2014 and CAN/CSA C22.2 No. 60950-1-07, Second Edition + A2:2014 (MOD), dated October 14, 2014
RoHS Compliant to RoHS EU Directive 2002/95/EC RoHS 6/6
EMC European Directive 2014/30/EU; EN55032, Class A; EN55035; FCC, Class A; GR1089-CORE ISSUE 6
10
Innity S Ordering Guide | www.gecriticalpower.com
MECHANICAL
Height 4RU main cabinet plus 1RU per power shelf – Base system 5RU (8.75 inches / 222mm)
Width (with mounting ears) 23 inches (584mm)
Depth 18 inches (457mm), 21 inches (533mm) for systems equipped with AC5 input
Weight (without rectiers) Approximately 42lbs (19kg) – Base system with 1 rectier shelf
AGENCY CERTIFICATIONS
UL ISSUE 6
EMI/EMC European Directive 2014/30/EU; EN55032 (CISPR22) Class A; EN55035 (CISPR24)
NEBS LEVEL 3 GR1089-CORE ISSUE 6
CC848815341 Advanced Features User Guide for the Pulsar Plus Controller, 167-792-183
CC848908475 Innity S Quick Start Guide
850022389 Innity S Quick Start Guide, Dual Voltage Systems
CC848836981 User Guide for the Galaxy Pulsar Edge Family of System Controllers
ENVIRONMENTAL
NEBs Evaluated by independent NRTL test lab to Telcordia GR63-CORE and GR1089-CORE ISSUE 6 [Level 3]
Safety ANSI/UL60950-1-2014 and CAN/CSA C22.2 No. 60950-1-07, Second Edition + A2:2014 (MOD), dated October 14, 2014
RoHS Compliant to RoHS EU Directive 2002/95/EC RoHS 6/6
EMC European Directive 2014/30/EU; EN55032, Class A; EN55035; FCC, Class A; GR1089-CORE ISSUE 6
Shelf Specications
Additional Information
Product Documentation
11
Innity S Ordering Guide | www.gecriticalpower.com
Ordering Guide
Features
Innity S may be congured as a +24V or -48V single voltage power system or as a
dual voltage” power system that supports rectiers and converters. The primary
voltage is supported by +24V or -48V rectiers and battery reserve, while secondary
voltage is supported by DC-DC converters. The primary voltage capacity is 1,200A at
24V and 800A at 48V. Secondary voltage capacity is up to 120A (-48V), 300A (24V).
Innity S systems may be equipped in a 7ft framework, a half height (42”) frame
for mounting on battery stands, integrated into cabinet applications, or supplied
frameless for eld install applications.
Infinity Series Rectifiers for +24V and
-48V applications.
Dual Voltage Bus architecture for easy
growth and voltage migration
DC-DC Converter support for dual
voltage systems
DC Distribution for both voltages, with
Selectable Voltage panel availability
Temperature hardened harsh
environments. (-40ºC to +75ºC)
Compact size: Base System with 1
power shelf occupies 5 RU (8.75 in) of
19” or 23” rack space (18”-21” depth)
Frame options – Factory installed in
7ft or 42” tall, 19” or 23” wide frame or
field installed in user supplied frame
Battery connections, LVBD and
LVLD options.
Plug-N-Play Pulsar Plus controller with
Web based interface for local and
remote (LAN) access.
Distribution options include 3A-250A
bullet style circuit breakers, and
GMT fuses
Ordering Information – Innity S Power System
TYPE DESCRIPTION SCHEMATIC
AC1 Dual Feed, Molex Mini-t Sr
AC3 Individual Feed, IEC-320 C19 Receptacles
AC5 Individual Feed, Terminal Strip, 3/4” Conduit or Cord Grip
AC6 Three Phase, terminal strip input Rear cover is equipped with a 1” conduit knockout
AC Input Types
19” Shelves
23” Shelves
23” Shelves
19” Shelves
19” Shelves
23” Shelves
23” Shelves
12
Innity S Ordering Guide | www.gecriticalpower.com
-48V SINGLE VOLTAGE SYSTEMS
Type Description Schematic
DC1E Single External Bullet Breaker Distribution Panel
20 Positions for 19” conguration / 26 Positions for 23” conguration
Ratings: 400A output (400A discharge) for 19”, 600A output (600A discharge) for 23”, 250A max breaker (65°C Ambient)
DC2E Dual External Bullet Breaker Distribution Panel
40 Positions for 19” conguration / 52 Positions for 23” conguration
Ratings: 600A output (600A discharge) for 19”, 600A output (600A discharge) for 23”, 250A max breaker (65°C Ambient)
DC Output Types
DUAL VOLTAGE SYSTEMS
Type Description Schematic
DC1E Single External Dual Voltage Bullet Breaker Distribution Panel
26 Positions for 23” conguration
Ratings: 800A primary voltage output (800A discharge) and up to 300A secondary voltage output, 250A max breaker (65°C Ambient)
DC2E Dual External Dual Voltage Bullet Breaker Distribution Panel
52 Positions for 23” conguration
Ratings: 800A primary voltage output (800A discharge) and up to 300A secondary voltage output, 250A max breaker (65°C Ambient)
13
Innity S Ordering Guide | www.gecriticalpower.com
Step 1: Select the Base Power System
OUTPUT
RATING
DESCRIPTION AC INPUT LVD FRAME ORDERING
CODE
MODEL PHOTO
-48V
225A
225A Innity S Power
system equipped with 3
universal positions and
20 distribution positions
selectable between -48V
Load and Battery
System - 5RU
Ind. Term Block No 150033064 NES48-19-AC5-PS3-DC1E
3 Phase Term Block No 150033083 NES48-19-AC6-PS3-DC1E
Ind. Term Block LVBD 150032370 NES48-19-AC5-PS3-DC1E-LVBD
3 Phase Term Block LVBD 150033093 NES48-19-AC6-PS3-DC1E-LVBD
-48V
450A
450A Innity S Power
system equipped with 6
universal positions and
20 distribution positions
selectable between -48V
Load and Battery
System - 6RU
Ind. Term Block No 150033065 NES48-19-AC5-PS6-DC1E
3 Phase Term Block No 150033084 NES48-19-AC6-PS6-DC1E
Ind. Term Block LVBD 150033073 NES48-19-AC5-PS6-DC1E-LVBD
3 Phase Term Block LVBD 150033094 NES48-19-AC6-PS6-DC1E-LVBD
-48V
450A
450A Innity S Power
system equipped with
6 universal positions
and 40 total distribution
positions, 20 of which are
selectable between -48V
Load and Battery
System - 10RU
Ind. Term Block No 150033070 NES48-19-AC5-PS6-DC2E
3 Phase Term Block No 150033087 NES48-19-AC6-PS6-DC2E
Ind. Term Block LVBD 150033078 NES48-19-AC5-PS6-DC2E-LVBD
3 Phase Term Block LVBD 150033097 NES48-19-AC6-PS6-DC2E-LVBD
-48V
450A
450A Innity S Power
system equipped with 9
universal positions and and
20 distribution positions
selectable between -48V
Load and Battery
System - 7RU
Ind. Term Block No 150033066 NES48-19-AC5-PS9-DC1E
3 Phase Term Block No 150033085 NES48-19-AC6-PS9-DC1E
Ind. Term Block LVBD 150033074 NES48-19-AC5-PS9-DC1E-LVBD
3 Phase Term Block LVBD 150033095 NES48-19-AC6-PS9-DC1E-LVBD
-48V
600A
600A Innity S Power
system equipped with
9 universal positions
and 40 total distribution
positions, 20 of which are
selectable between -48V
Load and Battery
System - 11RU
Ind. Term Block No 150033071 NES48-19-AC5-PS9-DC2E
3 Phase Term Block No 150033088 NES48-19-AC6-PS9-DC2E
Ind. Term Block LVBD 150033079 NES48-19-AC5-PS9-DC2E-LVBD
3 Phase Term Block LVBD 150033098 NES48-19-AC6-PS9-DC2E-LVBD
Single Voltage System -48V, 19” Width
14
Innity S Ordering Guide | www.gecriticalpower.com
Step 1: Select the Base Power System (Cont.)
OUTPUT
RATING
DESCRIPTION AC INPUT LVD FRAME ORDERING
CODE
MODEL PHOTO
-48V
450A
450A Innity S Power
system equipped with
12 universal positions
and and 20 distribution
positions selectable
between -48V Load and
Battery
System - 8RU
Ind. Term Block No 150033067 NES48-19-AC5-PS12-DC1E
3 Phase Term Block No 150033086 NES48-19-AC6-PS12-DC1E
Ind. Term Block LVBD 150033075 NES48-19-AC5-PS12-DC1E-LVBD
3 Phase Term Block LVBD 150033096 NES48-19-AC6-PS12-DC1E-LVBD
-48V
600A
600A Innity S Power
system equipped with
12 universal positions
and 40 total distribution
positions, 20 of which are
selectable between -48V
Load and Battery
System - 12RU
Ind. Term Block No 150033072 NES48-19-AC5-PS12-DC2E
3 Phase Term Block No 150033089 NES48-19-AC6-PS12-DC2E
Ind. Term Block LVBD 150033080 NES48-19-AC5-PS12-DC2E-LVBD
3 Phase Term Block LVBD 150033099 NES48-19-AC6-PS12-DC2E-LVBD
-48V
450A
450A Innity S Power
system equipped with 15
universal positions and
20 distribution positions
selectable between -48V
Load and Battery
Additional rectier
positions intended for Eco
Priority solutions
System - 9RU
Ind. Term Block No 150033068 NES48-19-AC5-PS15-DC1E
Ind. Term Block LVBD 150033076 NES48-19-AC5-PS15-DC1E-LVBD
-48V
450A
450A Innity S Power
system equipped with 18
universal positions and
20 distribution positions
selectable between -48V
Load and Battery
Additional rectier
positions intended for Eco
Priority solutions
System - 10RU
Ind. Term Block No 150033069 NES48-19-AC5-PS18-DC1E
Ind. Term Block LVBD 150033077 NES48-19-AC5-PS18-DC1E-LVBD
Single Voltage System -48V, 19” Width
15
Innity S Ordering Guide | www.gecriticalpower.com
Step 1: Select the Base Power System (Cont.)
OUTPUT
RATING
DESCRIPTION AC INPUT LVD FRAME ORDERING
CODE
MODEL PHOTO
-48V
200A
200A Innity S Power
system equipped with 4
rectier positions and 26
distribution positions which
are selectable between
-48V Load and Battery
System - 5RU
Dual Molex No CC109163696 NES48 -23 -AC1 -PS4 -DC1E
Dual Molex LVBD CC109160438 NES48 -23 -AC1 -PS4 -DC1E -LVBD
-48V
300A
300A Innity S Power
system equipped with 4
rectier positions and 26
distribution positions which
are selectable between
-48V Load and Battery.
System - 5RU
Ind. Term Input No 150045731 NES48-23-AC5H-PS4-DC1E
Ind. Term Input LVBD 150045737 NES48-23-AC5H-PS4-DC1E-LVBD
-48V
400A
400A Innity S Power
system equipped with
8 rectier positions and
26 distribution positions
selectable between -48V
Load and Battery
System - 6RU
Dual Molex No CC109163705 NES48 -23 -AC1 -PS8 -DC1E
Dual Molex LVBD CC109165998 NES48 -23 -AC1 -PS8 -DC1E -LVBD
-48V
600A
600A Innity S Power
system equipped with
12 rectier positions and
26 distribution positions
selectable between -48V
Load and Battery
System - 7RU
Dual Molex No CC109163713 NES48 -23 -AC1 -PS12 -DC1E
Ind. Term Block No 150045733 NES48 -23 -AC5H -PS12 -DC1E
Ind. Term Block No 150045732 NES48-23-AC5H-PS8-DC1E
Dual Molex LVBD CC109167920 NES48 -23 -AC1 -PS12 -DC1E -LVBD
Ind. Term Block LVBD 150045739 NES48 -23 -AC5H -PS12 -DC1E -LVBD
Ind. Term Block LVBD 150045738 NES48-23-AC5H-PS8-DC1E-LVBD
-48V
600A
600A Innity S Power
system equipped with 12
rectier positions and 52
total distribution positions,
26 of which are selectable
between -48V Load
and Battery
System - 11RU
Dual Molex No CC109171286 NES48 -23 -AC1 -PS12 -DC2E
Dual Molex LVBD CC109171278 NES48 -23 -AC1 -PS12 -DC2E -LVBD
-48V
600A
600A Innity S Power
system equipped with
16 rectier positions and
26 distribution positions
selectable between -48V
Load and Battery
System - 8RU
Ind. Term Block No 150045735 NES48 -23 -AC5H -PS16 -DC1E
Ind. Term Block LVBD 150045742 NES48 -23 -AC5H -PS16 -DC1E -LVBD
-48V
800A
800A Innity S Power
system equipped with
16 rectier positions
and 52 total distribution
positions, 26 of which
are selectable between
-48V Load and Battery
System - 12RU
Ind. Term Block No 150045734 NES48-23-AC5H-PS12-DC2E
Ind. Term Block LVBD 150045740 NES48-23-AC5H-PS12-DC2E-LVBD
Ind. Term Block No 150045736 NES48 -23 -AC5H -PS16 -DC2E
Ind. Term Block LVBD 150045741 NES48-23-AC5H-PS12-DC2E-LVLD
Ind. Term Block LVBD 150045743 NES48 -23 -AC5H -PS16 -DC2E -LVBD
Single Voltage System -48V, 23” Width
16
Innity S Ordering Guide | www.gecriticalpower.com
Step 1: Select the Base Power System (Cont.)
OUTPUT
RATING
DESCRIPTION AC INPUT LVD FRAME ORDERING
CODE
MODEL PHOTO
-48V
+24V
400A
400A Innity S Power
system equipped with
8 universal positions
and 26 distribution
positions selectable
between -48V Load and
+24V Converter load
System - 6RU
Dual Molex No 150022649 NES4824-23-AC1-PS8-DC1E
Dual Molex LVBD 150022648 NES4824-23-AC1-PS8-DC1E-LVBD
-48V
+24V
600A
600A Innity S Power
system equipped with 8
universal positions and
26 distribution positions
selectable between
-48V Load and +24V
Converter load
System - 6RU
Ind. Term Block No 150045762 NES4824-23-AC5H-PS8-DC1E
Ind. Term Block Yes 150045763 NES4824-23-AC5H-PS8-DC1E-LVBD
Ind. Term Block No 84”
Zone 4
150045764 NES4824-23-AC5H-PS8-DC1E-7FTR
-48V
+24V
600A
600A Innity S Power
system equipped with 8
universal positions and 52
total distribution positions,
26 dedicated to -48V and
26 of which are selectable
between -48V Load and
+24V Converter load
System - 10RU
Ind. Term Block No 150045765 NES4824-23-AC5H-PS8-DC2E
Ind. Term Block LVBD 150045766 NES4824-23-AC5H-PS8-DC2E-LVBD
Ind. Term Block No 84”
Zone 4
150045767 NES4824-23-AC5H-PS8-DC2E-7FTR
-48V
+24V
600A
600A Innity S Power
system equipped with
16 universal positions
and 26 distribution
positions selectable
between -48V Load and
+24V Converter load
System - 8RU
Dual Molex No 150033376 NES4824-23-AC1-PS16-DC1E
Ind. Term Block No 150045768 NES4824-23-AC5H-PS16-DC1E
Dual Molex LVBD 150022650 NES4824-23-AC1-PS16-DC1E-LVBD
Ind. Term Block LVBD 150045769 NES4824-23-AC5H-PS16-DC1E-LVBD
Ind. Term Block No 150045770 NES4824-23-AC5H-PS16-DC1E-7FTR
-48V
+24V
800A
800A Innity S Power
system equipped with 16
universal positions and 52
total distribution positions,
26 dedicated to -48V and
26 of which are selectable
between -48V Load and
24V Converter Load
System - 12RU
Dual Molex No CC109172508 NES4824-23-AC1-PS16-DC2E
Ind. Term Block No 150045771 NES4824-23-AC5H-PS16-DC2E
Dual Molex LVBD CC109170643 NES4824-23-AC1-PS16-DC2E-LVBD
Ind. Term Block LVBD 150045772 NES4824-23-AC5H-PS16-DC2E-LVBD
Ind. Term Block No 84"
Zone 4
150045773 NES4824-23-AC5H-PS16-DC2E-7FTR
Ind. Term Block LVBD 84”
Zone 4
150045774 NES4824-23-AC5H-PS16-DC2E-
LVBD-7FTR
Ind. Term Block LVBD/
LVLD
84”
Zone 4
150045775 NES4824-23-AC5H-PS20-DC2E-
LVBD-LVLD-7FTR
Dual Voltage Innity S Power Systems,
-48V Primary with +24V Secondary 23” Width
OUTPUT
RATING
DESCRIPTION AC INPUT LVD FRAME ORDERING
CODE
MODEL PHOTO
+24V
-48V
800A
800A Innity S Power
system equipped
with 8 universal
positions and 26
distribution positions
selectable between
+24V Load and -48V
Converter Load
6RU
Dual Molex No CC109172524 NES2448-23-AC1-PS8-DC1E
Ind. Term Block No 150033378 NES2448-23-AC5-PS8-DC1E
Dual Molex LVBD CC109172516 NES2448-23-AC1-PS8-DC1E-LVBD
Ind. Term Block LVBD 150033379 NES2448-23-AC5-PS8-DC1E-LVBD
Ind. Term Block No 150036118 NES2448-23-AC5-PS8-DC1E-7FTR
+24V
-48V
800A
800A Innity S Power
system equipped
with 8 universal
positions and 52 total
distribution positions,
26 dedicated to +24V
and 26 of which are
selectable between
+24V Load and -48V
Converter Load
10RU
Ind. Term Block No 150033293 NES2448-23-AC5-PS8-DC2E
Ind. Term Block LVBD 150033294 NES2448-23-AC5-PS8-DC2E-LVBD
Ind. Term Block No 150036119 NES2448-23-AC5-PS8-DC2E-7FTR
+24V
-48V
900A
900A Innity S Power
system equipped with
16 universal positions
and 26 distribution
positions selectable
between+24V
Load and -48V
Converter Load
8RU
Dual Molex No CC109163135 NES2448-23-AC1-PS16-DC1E
Ind. Term Block No 150033380 NES2448-23-AC5-PS16-DC1E
Dual Molex LVBD CC109160818 NES2448-23-AC1-PS16-DC1E-LVBD
Ind. Term Block LVBD 150033381 NES2448-23-AC5-PS16-DC1E-LVBD
Ind. Term Block No 150036120 NES2448-23-AC5-PS16-DC1E-7FTR
+24V
-48V
1200A
1200A Innity S Power
system equipped with
16 universal positions
and 52 total distribution
positions, 26 dedicated
to +24V and 26 of
which are selectable
between +24V Load and
-48V Converter Load
System - 12RU
Dual Molex No CC109172540 NES2448-23-AC1-PS16-DC2E
Ind. Term Block No 150027197 NES2448-23-AC5-PS16-DC2E
Ind. Term Block No 150027197 NES2448-23-AC5-PS16-DC2E
Dual Molex LVBD CC109172532 NES2448-23-AC1-PS16-DC2E-LVBD
Ind. Term Block LVBD 150025861 NES2448-23-AC5-PS16-DC2E-LVBD
Ind. Term Block No 84"
Zone 4
150027198 NES2448-23-AC5-PS16-DC2E-7FTR
17
Innity S Ordering Guide | www.gecriticalpower.com
OUTPUT
RATING
DESCRIPTION ORDERING
CODE
MODEL PHOTO
+24V
30A
Innity S - 19” stand-alone -48V/+24V converter shelf.
The shelf has individual -48V DC inputs with +24V 6-GMT fuse outputs.
The shelf is rated for a maximum of 30A output.
1RU (Order Controller separately in Step 3)
150034774 J5964803L224
Step 1: Select the Base Power System (Cont.)
Innity S Converter Shelf,
-48V Primary with +24V Secondary 19” Width
Dual Voltage Innity S Power Systems,
+24V Primary with -48V Secondary 23” Width
18
Innity S Ordering Guide | www.gecriticalpower.com
OUTPUT
RATING
DESCRIPTION ORDERING
CODE
MODEL PHOTO
-48V
30A
Innity S - 19” stand-alone +24V/-48V converter shelf. The shelf has
individual +24V DC inputs with -48V 6-GMT fuse outputs. The shelf is rated
for a maximum of 30A output.
1RU (Order Controller separately in Step 3)
150035606 J5964803L225
OUTPUT ORDERING CODE MODEL PHOTO
-48V
+24V
150024099 RBA72 Power Node Cabinet
Includes the dual voltage Innity S power system that
is rated @ 550A N+1 and is capable of supporting 3
battery strings. (Battery Thermal Probes Included)
Using 3 strings of 180Ahr batteries, the batteries will
support 118.5A of load capacity.
-48V
150024100 RBA72-36 Supplemental Battery Cabinet
Supports up to 6 strings of batteries. Battery disconnect
panel in top of cabinet supports an individual 100A
disconnect per battery string. Using 6 strings of
180Ahr batteries, the batteries will support 237A of
load capacity. (No Battery Thermal Probes Included)
ORDERING CODE DESCRIPTION PHOTO
CC109172053 Bus Kit to add 10 battery connections; 4 - 5/16” on 1” and 6 - 1/4-20 on 5/8”
connections. (positive and negative buses included)
See Attached Drawing
850022254 Bus Kit to expand battery bulk connections on battery buses to 2 - 3/8” on 1”
through hole connections. (One bus per kit, order two for paired connections)
See Attached Drawing
(4) .434
3.50
1.60
R.19
2.00
.70
1.30
.50
1.00
.50
1.00
.60
(2) .35
.19 REF
2/1SCALE
Step 1: Select the Base Power System (Cont.)
Innity S Converter Shelf,
+24V Primary with -48V Secondary 19” Width
RBA72 Power and Battery Cabinets
Battery Bus Extension Kits -
Used for expanding battery bus connections in single voltage systems
19
Innity S Ordering Guide | www.gecriticalpower.com
Step 2: Select Rectiers and Converters
OUTPUT
RATING
ORDERING CODE MODEL PHOTO
100A
CC109160834 95 - 145Vac input, 24V, 44A output (max. 50A@24V)
175 - 305Vac input, 24V, 100A output (max. 114A @24V)
145 - 175 linear output increase from 44A to 100A
NE100AC24ATEZ
100A
150025075 95 - 145Vac input, 24V, 44A output (max. 50A@24V)
175 - 305Vac input, 24V, 100A output (max. 114A @24V)
145 - 175 linear output increase from 44A to 100A
100 - 310 VDC input from Solar resource with full power above 250VDC.
NE100ECO24ATEZ
50A
CC109158878 95 - 145Vac input, 48V, 22A output (max. 25A @48V)
175 - 305Vac input, 48V, 50A output (max. 57A @48V)
145 - 175 linear output increase from 22A to 50A
NE050AC48ATEZ
50A
150025074 95 - 145Vac input, 48V, 22A output (max. 25A @48V)
175 - 305Vac input, 48V, 50A output (max. 57A @48V)
145 - 175 linear output increase from 22A to 50A
100 - 310 VDC input from Solar resource with full power above 250VDC.
NE050ECO48ATEZ
75A
CC109163473 95 - 145Vac input, 48V, 22A output (max. 25A@48V)
175 - 305Vac input, 48V, 75A output (max. 82A@48V)
145 - 175 linear output increase from 22A to 75A
Note: for use in 19” or AC5H 23” systems only
NE075AC48ATEZ
Rectiers
ORDERING
CODE
DESCRIPTION PHOTO
150050584 NES AC3 19in Single Voltage Supplemental Shelf Kit Each kit includes: Rectier shelf with mounting
hardware, busbar interconnects with hardware and
inter-shelf communication cable
150041585 NES AC5 19in Single Voltage Supplemental Shelf Kit
150041586 NES AC6 19in Single Voltage Supplemental Shelf Kit
150041583 NES AC1 23in Single Voltage Supplemental Shelf Kit
150041584 NES AC5 23in Single Voltage Supplemental Shelf Kit
150041587 NES AC1 23in Dual Voltage Supplemental Shelf Kit
150041588 NES AC5 23in Dual Voltage Supplemental Shelf Kit
150050606 NES AC5H 23in Single Voltage Supplemental Shelf Kit
150050607 NES AC5H 23in Dual Voltage Supplemental Shelf Kit
Note: Adding these shelves does not increase the overall rating of the distribution.
Step 1: Select the Base Power System (Cont.)
Supplemental Rectier Shelf Kits -
Used for Installing Additional Rectier Shelves to an Innity S System in the Field
20
Innity S Ordering Guide | www.gecriticalpower.com
For Innity S Converter Shelves only, select a Pulsar Edge controller for managing and monitoring of the converter shelf.
ORDERING CODE DESCRIPTION MODEL
150036348 Pulsar Edge Controller with 6 output relays, USB port, and Display NE841E_016R_USB_DS
150041556 Pulsar Edge Controller with 6 output relays, USB port and NO graphic display) CNTL_NE841E_016R_USB_S
150039541 Pulsar Edge Controller with 3 input and 3 output relays, USB port and NO graphic display. CNTL_NE841E_3C3R_USB_S
Step 3: Select Controller
OUTPUT
RATING
ORDERING CODE MODEL PHOTO
30A
CC109112471 21-30Vdc input, 48V, 30A output
NE030DC48A
40A
150023619 21-30Vdc input, 48V, 40A output
NE040DC48AZ
75A
CC109142881 42-60Vdc input, 24V, 75A output
NE075DC24A
Converters
ORDERING CODE MODEL
CC109170668 Innity Rectier/Converter slot ller (full chassis)
CC848798702 Blank panel for use in empty rectier / converter positions
Miscellaneous
Step 2: Select Rectiers and Converters (Cont.)
21
Innity S Ordering Guide | www.gecriticalpower.com
The following AC Covers can be used to replace the individual AC Covers on the 23” AC5 or AC5H shelf with a single larger
cover to allow for fewer conduit runs to the system. Each Kit comes with 2 covers, one for each side of the system.
Example: 208/240VAC for a NES48-AC1-PS4-DC1E-LVBD shelf using 50A rectiers would use a 848710711 AC
8 gauge which provides 2 AC cords; enough to power 4 rectiers. Customer should provide one 40A protecting
circuit breaker per two rectiers. For AC3 cable sets, it is recommended that a 20A circuit breaker is used per
rectier. Note: If PS# of your shelf model number is not listed in table, choose the next higher number. AC cords
are 10 feet long and unterminated on the end. See optional accessories for twist lock connectors.
ORDERING
CODE
AC
TYPE
GAUGE SHELF
TERMINATION
ORDER # OF CORDS CORD
TYPE
LENGTH USER
TERMINATION
120 VAC 208/240
VAC
SHELF DUAL INDIV.
CC848801977 AC1 8 Molex 1 x Sleeved 3' Unterminated x x
CC848830522 Molex 1 x Sleeved 4' Unterminated
848710711 Molex 1 x Sleeved 10' Unterminated
CC848906586 Molex 2 x SO 10' Unterminated
CC848773515 10 Molex 2 x SO 15' Unterminated
850031034 8 Molex 2 x SO Unterminated
CC848847368 AC3 12 IEC - No Plug 4 x SO 8’ Unterminated x x
CC848850801 12 IEC 5 - 20P 4 x SO 8’ 5 -20P x
CC848850834 12 IEC 6 - 20P 4 x 8’ 6 -20P x
CC848850842 12 IEC L6 - 20P 4 x 8’ L6 -20P x
ORDERING CODE AC COVER KIT
150037979 2 Shelf AC Cover Kit
150037980 3 Shelf AC Cover Kit
150037981 4 Shelf AC Cover Kit
Step 4: Select AC Accessories
ORDERING CODE MODEL PHOTO
CC848865980 15ft Auxiliary input alarm cable for Pulsar Plus Controller
CC848817651 50ft Auxiliary input alarm cable for Pulsar Plus Controller
CC848817668 150ft Auxiliary input alarm cable for Pulsar Plus Controller
CC109157442 15ft alarm cable for Pulsar Plus Controller
CC848817635 50ft alarm cable for Pulsar Plus Controller
CC848817643 150ft alarm cable for Pulsar Plus Controller
CC848890161 5ft alarm cable for Pulsar Edge Controller
CC848890178 15ft alarm cable for Pulsar Edge Controller
CC848890186 50ft alarm cable for Pulsar Edge Controller
Step 5: Select Alarm Cables
Alarm Cables
22
Innity S Ordering Guide | www.gecriticalpower.com
Step 6: Select Distribution Components
Innity S systems all support plug-in (bullet style) breakers or fuse modules. Larger breakers can be 2 or even 3 poles.
The multi-pole breakers MUST be used with the appropriate multi-pole adapter to parallel the poles for proper operation.
ORDERING CODE AMPERAGE CB POSITIONS (POLES) MIN WIRE GAUGE PHOTO
407998137 3 1 10
407998145 5 1 10
407998152 10 1 10
407998160 15 1 10
407998178 16 1 10
407998186 20 1 10
407998194 25 1 10
407998202 30 1 10
408213486 40 1 8
407998210 45 1 8
407998228 50 1 6
407998236 60 1 6
407998244 70 1 2
407998251 80 1 2
407998269 90 1 2
407998277 100 1 2
CC848808551 100 2 2
408185353 125 2 2
408185346 150 2 1/0
408564941 200 3 2/0
CC408573975 225 3 4/0
408535752 250 3 4/0
CC848756916 2-pole Adapter bus for 100-150A breakers; used for ¼”-20 on 5/8” lugs
(order 2 per 2 pole breaker to accommodate load and return lugs)
850021775 2-pole Adapter bus for 100-150A breakers; used for 3/8” on 1” lugs
(order 2 per 2 pole breaker to accommodate load and return lugs)
CC848756924 3-pole Adapter bus for 200-250A breakers; used for 3/8” on 1” lugs;
o-center connection
(order 2 per 3 pole breaker to accommodate load and return lugs)
850021955 3-pole Adapter bus for 200-250A breakers; used for 3/8” on 1” lugs;
center connection
(order 2 per 3 pole breaker to accommodate load and return lugs)
Note: For 70-100A single pole breakers, one breaker space must be left open in the adjacent position when powering breaker above 80% capacity under normal loading conditions
Bullet Style Load Circuit Breakers
23
Innity S Ordering Guide | www.gecriticalpower.com
ORDERING CODE AMPERAGE WP-92461 LIST MIN WIRE GAUGE PHOTO
406700567 3 100 10
406700583 5 101 10
406700591 6 102 10
406700609 10 103 10
406700617 15 104 10
406700625 20 105 10
406700633 25 106 10
406700641 30 107 10
406700658 40 108 10
406700674 50 109 8
406700682 60 110 6
406700690 70 111 6
402328926 0.18 Alarm Fuse
408548944 Bullet Fuse Holder, TFD-101-011-09
(Alarms on Blown Fuse or Fuse Head Removal)
CC408617410 Bullet Fuse Holder, TFD-101-011-10 (Alarms on Blown Fuse Only)
Step 6: Select Distribution Components (Cont.)
ORDERING CODE AMPERAGE PHOTO
CC408612758 30
CC408612766 40
CC408612774 45
CC408574370 50
408560123 60
CC408574387 70
CC408574395 100
CC408574404 125 (2-pole)
CC408574412 150 (2-pole)
CC408574420 200 (2-pole)
CC408645295 250A (3-pole)
CC109106548 100A battery bullet bus strap (substitute for battery breaker)
Bullet Battery Circuit Breakers (Yellow Handle)
(Alarms on Mid-Trip and in O Position)
Bullet Style Fuse Holder and TPS Fuses
24
Innity S Ordering Guide | www.gecriticalpower.com
Step 6: Select Distribution Components (Cont.)
Bullet Style GMT Fuse Holder and GMT Fuses
ORDERING CODE AMPERAGE PHOTO
405006222 0.25A
3150439 0.5A
405673146 1.33A
405181983 2A
406976985 3A
406159061 5A
405725433 7.5A
406159236 10A
407845197 12A
406473959 15A
CC109103157 6-pos GMT Bullet Fuse Holder (Requires 2 bullet postions)
12A max. fuse
408515823 Fuse Puller
402099436 Dummy Fuse
Terminal Lugs for Bullet Style Breakers and TPS Fuses (1/4” Bolt on 5/8” Centers)
ORDERING CODE STR WIRE GA (CLASS B) FLEX WIRE GA (CLASS I) WP-91412 LIST PHOTO
406021626 8 8 75
405347519 6 6 3
405347576 4 4 5
405348202 2 - 54
405347683 - 2 8
Terminal Lugs for Battery and Large Breakers (3/8” Bolt on 1” Centers)
PEOPLESOFT NUMBER STR WIRE GA (CLASS B) FLEX WIRE GA (CLASS I) WP-91412 LIST PHOTO
406338665 2 - -
405348228 1/0 - -
405348236 2/0 1/0 -
406021725 - 2/0 -
405348251 4/0 - -
405347923 - 4/0 -
25
Innity S Ordering Guide | www.gecriticalpower.com
Step 7: Select Battery Monitoring
ORDERING CODE DESCRIPTION PHOTO
CC109142980 QS873A Thermal Probe (A)
150026698 QS873B Ambient Thermal Probe (A)
CC848817024 10 ft wire set (B: thermal probe to controller)
CC109157434 20 ft wire set (B: thermal probe to controller)
CC848822560 1 ft wire set (C: thermal probe to thermal probe)
848719803 5 ft wire set (C: thermal probe to thermal probe)
CC848822321 10 ft wire set (C: thermal probe to thermal probe)
850027334 20 ft wire set (C: thermal probe to thermal probe)
108958422 ES771A Battery Voltage Monitor Card
CC848791517 2-1/2 ft wire set (D: ES771A to thermal probe)
CC848797290 6 ft wire set (D: ES771A to thermal probe)
848719829 10 ft wire set (D: ES771A to thermal probe)
CC848791500 4 ft wire set (G: ES771A to ES771A or controller)
848652947 10 ft wire set (G: ES771A to ES771A or controller)
555052-1 In-Line Coupler (for extending item G above)
Temperature/Voltage probes are needed for battery monitoring. They are connected to each battery or battery string to provide slope thermal compensation,
temperature alarms and voltage imbalance alarms.
Temperature Measurement
Temperature and Voltage Measurement
26
Innity S Ordering Guide | www.gecriticalpower.com
Notes
27
Innity S Ordering Guide | www.gecriticalpower.com
Notes
Management Visibility
Galaxy Manager* software is the centralized visibility and control component
of a comprehensive power management system designed to meet engineering,
operations and maintenance needs. The Galaxy Manager client-server architecture
enables remote access to system controllers across the power network.
Dashboard display with one-click access to
management information database
Trend analysis
Scheduled or on demand reports
Fault, configuration, asset, and performance management
Training
GE oers on-site and classroom training options based on certication curriculum.
Technical training can be tailored to individual customer needs. Training enables
customers and partners to more eectively manage and support the power
infrastructure. We have built our training program on practical learning objectives
that are relevant to specic technologies or infrastructure design objectives.
Service & Support
GE eld service and support personnel are trusted advisors to our customers
– always available to answer questions and help with any project, large or
small. Our certied professional services team consists of experts in every
aspect of power conversion with the resources and experience to handle
large turnkey projects along with custom approaches to complex challenges.
Proven systems engineering and installation best practices are designed
to safely deliver results that exceed our customers’ expectations.
Warranty
GE is committed to providing quality products and solutions. We have
developed a comprehensive warranty that protects you and provides a
simple way to get your products repaired or replaced as soon as possible.
For full warranty terms and conditions please go to
www.gecriticalpower.com.
Reliability
Distributed fault tolerance
Proven field performance
Controller continuity
Intelligence
Industry leading controller features
Ethernet interface for remote access
Centralized network management
Investment Protection
Module Compatibility
Secondary Voltage
flexibility +24V / -48V
Flexible Upgrade Options
On Time Delivery
Standard building blocks
4 - 6 week availability
24/7 technical support
*Registered trademark of the General Electric Company.
The GE brand, logo, and lumination are trademarks of the General Electric Company. © 2016 General Electric Company.
Information provided is subject to change without notice. All values are design or typical values when measured under
laboratory conditions.
CPB-NES, Rev. 04/2016
Critical Power from GE
601 Shiloh Road
Plano, TX 75074
+1 877 546 3243
www.gecriticalpower.com