Saving Lives through innova
tion & educa
tion
❘ Hilti F
irestop Guide 2005–2006
❘ 1-800-363-4458 ❘ www
.ca.hilti.com
Product Information
INTRODUCTION
APPLICATIONS / PRODUCTS
SYSTEM DETAILS
ESTIMA
TING TABLES / TECH DATA
7
29
|latest product infor
mation :
www.ca.hilti.com
|or
dering infor
mation see page:
1. Clean opening. 2. Pack mineral
wool. (If required)
3. Apply FS-ONE. 4. Smooth FS-ONE. 5.
Leave completed
seal undisturbed for
48 hours.
6. Fasten identifi-
cation plate (if
required).
1. Clean opening. 2. Pack mineral
wool. (If required)
3.
A
pply FS-ONE. 4. Smooth FS-ONE. 5.
Lea
ve completed
seal undisturbed for
48 hours.
6.
F
asten identifica-
tion plate (if
required).
Product description
•
Intumescent (expands when exposed to fire) firestop sealant
that helps protect combustible and non-combustible penetra-
tions for up to 4 hours fire rating
Product features
• Smoke, gas and water resistant after material has cured
•
Contains no halogen, solvents or asbestos
• High fire rating properties
• Water based, easy to clean
Areas of application
• Steel, copper and EMT pipes
• Insulated steel and copper pipes
• Cable bundles
• Closed or vented plastic pipes (50 pa. test)
• HVAC penetrations
For use with
• Concrete, masonry, drywall and wood floor assemblies
• Wall and floor assemblies rated up to 4 hours
Examples
•
Sealing around plastic pipe penetrations in fire rated
construction
• Sealing around combustible and non-combustible
penetrations in fire rated construction
FS-ONE
Technical Data
At 73°F (23°C) and 50% relative humidity
Chemical basis
Water-based intumescent acrylic dispersion
Density
Approx. 1.5 g/cm
3
Color
Red
W
orking time
Approx. 20-30 min.
Curing time
Approx. 2 mm / 3 days
Shore A Hardness
Approx. 50
Movement capability
Approx.
5%
Intumescent Activation
Approx 482°F (250°C)
Expansion rate (unrestricted):
Up to 3-5 times original volume
Temperature resistance (cured)
–40°F to 212°F (–40°C to 100°C)
Application temperature
41°F to 104°F (5°C to 40°C)
Surface burning characteristics
(ASTM E 84-96)
Flame Spread: 0
Smoke Development: 5
Sound transmission classification
(ASTM E 90-99) 56
Tested in accordance with
• UL 1479
• ASTM E 814
• ASTM E 84
• CAN4-S115-95M
Internationally tested and approved
FS-ONE
High Performance
Intumescent Firestop
Sealant
Opening
1. Clean the opening. Surfaces to which FS-ONE will be
applied should be cleaned of loose debris, dirt, oil,
moisture, frost and wax. Structures supporting
penetrating items must be installed in compliance with
local building and electrical standards.
Application of firestop sealant
2. Install the prescribed backfilling material type and depth
to obtain the desired rating (if required). Leave sufficient
depth for applying FS-ONE.
3. Application of firestop sealant: Apply FS-ONE to the
required depth in order to obtain the desired fire rating.
Make sure FS-ONE contacts all surfaces to provide
maximum adhesion. For application of FS-ONE use a
standard caulking gun, foil pack gun, bulk loader and
bulk gun. With FS-ONE buckets, Graco type sealant
pumps ma
y be used.
(Contact pump manufacturer f
or
proper selection).
4. Smoothing of firestop sealant: To complete the seal, tool
immediately to give a smooth appearance. Excess
sealant, prior to curing, can be cleaned away from
adjacent surfaces and tools with water.
5. Leave completed seal undisturbed for 48 hours.
6. For maintenance reasons, a penetration seal could be
permanently marked with an identification plate. In such
a case, mark the identification plate and fasten it in a
visible position next to the seal.
Notice about approvals
• Check that the penetration has been sealed according to
the specified drawing in the UL/cUL Fire Resistance
Directory or Hilti Firestop Manual. For further advice,
please contact Hilti customer service. Refer to Hilti
product literature and UL fire resistance directory for
specific application details.
Not for use...
• High movement expansion joints
• Underwater
• On materials where oil, plasticizers or solvents may
bleed i.e. impregnated wood, oil based seals, green or
partially vulcanized rubber
• In any penetration other than those specifically
described in this manual or the test reports
Safety precautions
• Before handling, read the product and Material Safety
Data Sheet for detailed use and health information
• Keep out of reach of children
• Wear suitable gloves and eye protection
Storage
• Store only in the original packaging in a location
protected from moisture at temperatures between
40°F (5°C) and 86°F (30°C)
• Observe expiration date on the packaging
Installation instructions for FS-ONE
Firestop
System
Firestop
System
CABLEPIPE
System Adv
antage / Customer Benefits
• Protects most typical firestop
penetration applications
• Easy to work with and fast cleanup
• Can be painted
• Single component systems available
FILL, VOID OR CAVITY MATERIAL
FOR USE IN
THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FM
APPROVED
For Penetration Fire Stops.
Consult the Factory Mutual Research Corporation Approval Guide.
R
C
L
A
S
S
I
F
I
E
D
FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
UNDERSRITERS LABOR
TORIES OF CANADA
LISTED FIRESTOP SYSTEM COMPONENT 00729A
FOR USE
AS
A COMPONENT IN
THE
APPROPRIA
TE
FIRESTOP SYSTEMS.
FOR DET
AILS OF FIRE RATED
SYSTEMS SEE ULC LIST OF EQUIPMENT AND
MA
TERIALS,
VOLUME III FIRE RESIST
ANCE RA
TINGS
(AND SUPPLEMENT
THERETO)