Table Of Contents
UL Listings
C-AJ-1664 (Canada Only).................................................................................................................... 1
C-AJ-4106 (Canada Only).................................................................................................................... 2
C-AJ-8248 (Canada Only).................................................................................................................... 3
C-BJ-1069 (Canada Only).................................................................................................................... 9
W-J-0024 (Canada Only)....................................................................................................................11
W-J-4078 (Canada Only)....................................................................................................................12
W-L-0048 (Canada Only)....................................................................................................................13
W-L-1518 (Canada Only)....................................................................................................................14
W-L-1519 (Canada Only)....................................................................................................................15
W-L-8104 (Canada Only)....................................................................................................................16
CFS-BL
Product Data Sheet for CFS-BL Firestop Block..................................................................................21
UL Certificate of Compliance for CFS-BL Firestop Block................................................................... 22
LEED Information for CFS-BL Firestop Block.....................................................................................23
CP 648-E (Endless)
Product Data Sheet for CP 648-E Firestop Wrap Strip.......................................................................24
UL Certificate of Compliance for CP 648-E and CP 648-S Firestop Wrap Strip.................................25
LEED Information for CP 648-S and CP 648-E Firestop Wrap Strip.................................................. 26
CP 660
UL Certificate of Compliance for CP 660 Firestop Foam....................................................................27
Hilti Firestop Systems
System No. C-AJ-4106
SECTION A-A
CAJ 4106
1. Floor or Wall Assembly — Min 114 mm (4-1/2 in.) thick reinforced lightweight or normal weight (1600-2400 kg/m3 or 100-150 pcf) concrete. Wall
may also be constructed of any UL Classified Concrete Blocks*. Max area of opening is (1445 cm2 or 224 in2) with max dimension of 813 mm (32
in.).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Cable Tray* — Max 610 mm (24 in.) wide by 102 mm (4 in.) deep open-ladder cable tray with channel-shaped side rails formed of 2.54 mm thick
aluminum and 38 mm (1-1/2 in.) wide by 25 mm (1 in.) channel shaped rungs spaced on 229 mm (9 in.) OC. The annular space between cable
tray and periphery of opening shall be min 0 mm (point contact) to max 127 mm (5 in.). Cable tray to be rigidly suported on both sides of wall
assembly.
3. Cables — Aggregate cross-sectional area of cable tray to be max 45 percent of the cross-sectional area of the cable tray. Any combination of the
following types and sizes of copper conductor cables may be used:
A. Max 300 pair No. 24 AWG telephone cable with polyvinyl chloride (PVC) insulation and jacket.
B. Max 500 kcmil single conductor copper power cable with PVC jacket material.
C. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 9.5 mm (3/8 in.)
D. Max 3/C No. 12 AWG copper conductor steel clad cable with PVC insulation material.
4. Firestop System — The firestop system shall consist of the following:
A. Fill, Void or Cavity Materials* — Foam — Min 127 mm (5 in.) thickness of fill material applied within the annulus, extending 13 mm (1/2 in.)
above the top surface of the floor or both surfaces of wall and overlapping the concrete 13 mm (1/2 in.) on all sides of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
B. Fill, Void or Cavity Materials — (Optional — Not Shown) — Nom 51 mm (2 in.) deep Fire Blocks applied in a single layer above cables within
cable tray with 127 mm (5 in.) dimension projecting through the opening and long dimension parallel to floor or wall. Either one or a
combination of the block types specified below may be used.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS 657 Fire Block or CFS-BL Firestop Block
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
A
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
F Rating - 2 Hr
T Rating - 0 Hr
FH Rating - 0 Hr
FTH Rating - 0 Hr
A
CANADA ONLY
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to CAN/ULC-S115
4
3
2
1
4
Hilti Firestop Systems
System No. C-AJ-8248
CAJ8248
Page: 1 of 6
D
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
F Rating - 2 Hr
FT Rating - 0, 1/2 and 2 Hr (See Item 2)
FH Rating - 0 Hr
FTH Rating - 0 Hr
D
EE
FF
CC
AA
GG
BB
CANADA ONLY
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to CAN/ULC-S115
Page: 2 of 6
Hilti Firestop Systems
SECTION A-A
System No. C-AJ-8248
CAJ8248
SECTION B-B
SECTION C-C SECTION D-D
2
3
2
4B
4A
3
1
2
3A
3B
3
2
3
1
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
FIRESTOP CONFIGURATION A FIRESTOP CONFIGURATION B
FIRESTOP CONFIGURATION DFIRESTOP CONFIGURATION C
CANADA ONLY
Page: 3 of 6
Hilti Firestop Systems
System No. C-AJ-8248
CAJ8248
SECTION E-E SECTION F-F
SECTION G-G
3
2
4
1
3
2
3
2
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
FIRESTOP CONFIGURATION FFIRESTOP CONFIGURATION E
FIRESTOP CONFIGURATION G
CANADA ONLY
Page: 4 of 6
1. Floor or Wall Assembly — Min 114 mm (4-1/2 in.) thick reinforced lightweight or normal weight (1600-2400 kg/m3 or 100-150 pcf) concrete.
Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of 3871 cm2 (600 in2) with max dimension of 762 mm (30 in.).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants — A max of seven firestop configurations may be installed within the opening. The space between firestop configurations
shall be as specified in the individual configurations. Unless otherwise indicated, the space between firestop configurations and periphery of
opening shall be min 13 mm (1/2 in.) to max 140 mm (5-1/2 in.). Pipe, conduit, tubing or cables to be rigidly supported on both sides of floor or
wall assembly. The T Rating of the system is dependent on the firestop configurations, as shown in the table below. Any combination of the
following firestop configurations detailed herein may be used:
Firestop Configuration A
2. Cables — Max 102 mm (4 in.) diam of tightly bundled cables. The min annular space between adjacent penetrants shall be 102 mm (4 in.).
Cable bundle may be any combination of the following types and sizes of cables:
A. Max 300 pair No. 24 AWG copper telephone cables with polyvinyl chloride (PVC) insulation and jacket materials.
B. Max 500 kcmil single conductor copper power cable with PVC jacket material.
C. Max 7/C No. 12 AWG cable with polyvinyl PVC insulation and jacket materials.
D. Multiple fiber optical communication cables with PVC jacket material and having a max outside diameter of 3/8 in.
E. Max 3/C No. 12 AWG steel clad cables with PVC insulation materials.
F. Max 3/C No. 10 AWG cables with ground with PVC insulation and jacket materials.
3. Fill, Void or Cavity Materials* — Foam — Min 127 mm (5 in.) thickness of fill material applied within the annulus, extending 13 mm (1/2 in.)
above the top surface of the floor or both surfaces of wall and overlapping the concrete 13 mm (1/2 in.) on all sides of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
Firestop Configuration B
2. Copper Tube or Pipe — Nom 51 mm (2 in.) diam (or smaller) Type L copper tube or nom 51 mm (2 in) diam (or smaller) Regular (or heavier)
copper pipe. Min space between adjacent penetrants shall be 76 mm (3 in.).
3. Tube Insulation-Plastics+ — Nom 19 mm (3/4 in.) thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form
of tubing. The min space between adjacent penetrants shall be 76 mm (3 in.). See Plastics+ (QMFZ2) category in the Plastics Recognized
Component Directory for names of manufacturers. Any Recognized Component tube insulation material meeting the above specifications and
having a UL 94 Flammability Classification of 94-5VA may be used.
4. Firestop System — The firestop system shall consist of the following:
A. Fill, Void or Cavity Material* — Wrap Strip — Min 25 mm (1 in.) wide wrap strip applied in a single wrap installed flush with bottom surface
of floor or extending 1/2 in. beyond both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 648E Wrap Strip
B. Fill, Void or Cavity Materials* — Foam — Min 127 mm (5 in.) thickness of fill material applied within the annulus, extending 13 mm (1/2
in.) above the top surface of the floor or both surfaces of wall and overlapping the concrete 1/2 in. on all sides of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
Hilti Firestop Systems
System No. C-AJ-8248
CAJ8248
Firestop Configuration
T Rating Hr
A 1/2
B 1/2
C
0
D
0
E 2
F 1/2
G
0
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
CANADA ONLY
Page: 5 of 6
Hilti Firestop Systems
Firestop Configuration C
2. Polyvinyl Chloride (PVC) Pipe — Nom 102 mm (4 in.) diam (or smaller) Schedule 40 solid or cellular core PVC pipe for used in closed
(process or supply) or vented (drain, waste or vent) piping systems. The min space between adjacent penetrants shall be 114 mm (4-1/2 in.).
3. Firestop System — The firestop system shall consist of the following:
A. Fill, Void or Cavity Material* — Wrap Strip — Two stacks of min 44 mm (1-3/4 in.) wide wrap strips, each applied in a single wrap and
tightly butted, installed flush with bottom surface of floor or both surfaces of wall or extending 13 mm (1/2 in.) beyond both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 648E Wrap Strip
B. Fill, Void or Cavity Materials* — Foam — Min 127 mm (5 in.) thickness of fill material applied within the annulus flush with bottom surface
and extending 13 mm (1/2 in.) above the top surface of the floor or extending 13 mm (1/2 in.) beyond both surfaces of wall and
overlapping the concrete 13 mm (1/2 in.) on all sides of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
Firestop Configuration D
2. Through Penetrant — One metallic pipe, conduit or tube to be installed either concentrically or eccentrically within the firestop system. The
min annular space between the pipe, conduit of tube and periphery of opening shall be 0 mm (point contact). The min space between adjacent
penetrants shall be 102 mm (4 in.). Pipe, conduit of tube to be rigidly supported on both sides of floor or wall assembly. The following types
and sizes of metallic pipes, conduits or tubes may be used:
A. Nom 102 mm (4 in.) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Nom 102 mm (4 in.) diam (or smaller) cast or ductile iron pipe.
C. Nom 102 mm (4 in.) diam (or smaller) rigid steel conduit.
D. Nom 102 mm (4 in.) diam (or smaller) steel electrical metallic conduit.
E. Nom 102 mm (4 in.) diam (or smaller) Type L (or heavier) copper tubing.
F. Nom 102 mm (4 in.) diam (or smaller) Regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* — Foam — Min 127 mm (5 in.) thickness of fill material applied within the annulus, extending 13 mm (1/2 in.)
above the top surface of the floor or both surfaces of wall and overlapping the concrete 13 mm (1/2 in.) on all sides of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
Firestop Configuration E
2. Steel Pipe — Nom 203 mm (8 in.) diam (or smaller) Schedule 40 (or heavier) steel pipe.
3. Pipe Covering Materials* — Nom 38 mm (1-1/2 in.) thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside
with an all-service jacket. Longitudinal joints sealed with metal fasteners or factory-applied, self-sealing lap tape. Transverse joints secured
with metal fasteners of with butt tape supplied with product. The min space between adjacent penetrants shall be 76 mm (3 in.).
See Pipe and Equipment Covering - Materials (BRGU) Category in the Building Materials Directory for names of manufacturers. Any pipe
covering meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a
Smoke Developed Index of 50 or less may be used.
4. Fill, Void or Cavity Materials* — Foam — Min 127 mm (5 in.) thickness of fill material applied within the annulus, extending 13 mm (1/2 in.)
above the top surface of the floor or both surfaces of wall and overlapping the concrete 13 mm (1/2 in.) on all sides of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
Firestop Configuration F
2. Cable — Nom 51 mm (2 in.) diam (or smaller) TEK cable with cross-linked polyethylene insulation. The min space between adjacent
penetrants shall be 76 mm (3 in.).
3. Fill, Void or Cavity Material* — Foam — Min 127 mm (5 in.) thickness of fill material applied within the annulus, extending 13 mm (1/2 in.)
above the top surface of the floor or both surfaces of wall and overlapping the concrete 13 mm (1/2 in.) on all sides of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
System No. C-AJ-8248
CAJ8248
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
CANADA ONLY
Hilti Firestop Systems
Page: 6 of 6
Firestop Configuration G
2. Flexible Conduit — Nom 25 mm (1 in.) diam (or smaller) flexible aluminum conduit. The min space between adjacent penetrants shall be 127
mm (5 in.).
3. Fill, Void or Cavity Material* — Foam — Min 127 mm (5 in.) thickness of fill material applied within the annulus, extending 13 mm (1/2 in.)
above the top surface of the floor or both surfaces of wall and overlapping the concrete 13 mm (1/2 in.) on all sides of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
+ Bearing the UL Listing Mark
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
System No. C-AJ-8248
CAJ8248
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
CANADA ONLY
Hilti Firestop Systems
System No. C-BJ-1069
SECTION A-A
CBJ1069
Page: 1 of 2
1. Floor or Wall Assembly — Min 152 mm (6 in.) thick reinforced lightweight or normal weight (1600-2400 kg/m3 or 100-150 pcf) concrete. Wall may
also be constructed of any solid or filled UL Concrete Blocks*. Max diameter of opening is 254 mm (10 in.).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Through Penetrants — One metallic pipe to be installed either concentrically or eccentrically within the firestop system. The annular space shall
be min 0 mm (point contact) to max 35 mm (1-3/8 in.). Pipe to be rigidly supported on both sides of the floor or wall assembly. The following types
and sizes of metallic pipes may be used:
A. Steel Pipe — Nom 203 mm (8 in.) diam (or smaller) Schedule 40 (or heavier) steel pipe.
B. Iron Pipe — Nom 203 mm (8 in.) diam (or smaller) cast or ductile iron pipe.
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
F Rating - 2 Hr
FT Rating - 2 Hr
FH Rating - 0 Hr
FTH Rating - 0 Hr
AA
30"
2
1
3B
3A
3C
CANADA ONLY
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to CAN/ULC-S115
Page: 2 of 2
3. Firestop System — The firestop system shall consist of the following:
A. Packing Material — Min 25 mm (1 in.) thickness of 64 kg/m3 (4 pcf) mineral wool batt insulation tightly packed into the opening as a
permanent form. Packing material to be recessed from top surface of floor as required to accommodate the required thickness of fill
material. Packing material not required in walls.
B. Fill, Void or Cavity Materials* — Foam — Min 127 mm (5 in.) thickness of fill material applied within the annulus, flush with top surface of
floor or min 152 mm (6 in.) thickness of fill material applied within the annulus, flush with both surfaces of wall. Additional fill material shall
extend above the top surface of the floor in accordance with the following table and shall overlap the concrete 13 mm (1/2 in.) around the
perimeter of the opening.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
Hilti Firestop Systems
System No. C-BJ-1069
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
CBJ1069
Concrete Thickness - mm (In.)
Foam Extension Above
Surface - mm (In.)
152 (6) 102 (4)
178 (7) 76 (3)
203 (8) 51 (2)
229 (9) 25 (1)
254 (10)
None
C. Pipe Covering Materials* — Nom 51 mm (2 in.) thick unfaced mineral fiber pipe insulation sized to the outside diam of pipe or tube. Pipe
insulation shall extend 762 mm (30 in.) along length of pipe, flush with lower surfaces of floor or both surfaces of wall. Pipe insulation
secured with nom 16 AWG steel wire spaced max 152 mm (6 in.) OC.
IIG MINWOOL L L C — High Temperature Pipe Insulation 1200, High Temperature Pipe Insulation BWT or High Temperature Pipe Insulation
Thermaloc
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
CANADA ONLY
Hilti Firestop Systems
System No. W-J-0024
SECTION A-A
WJ0024
1. Wall Assembly — Min 121 mm and 152 mm (4-3/4 in. and 6 in.) thick reinforced lightweight or normal weight (1600-2400 kg/m3 or 100-150 pcf)
concrete for 1 and 2 hr fire rated walls, respectively. Wall may also be constructed of any solid or filled UL Classified Concrete Blocks*. Max area
of opening is 2903 cm2 (450 in2) with max dimension of 762 mm (30 in.).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Fill, Void or Cavity Materials* — Foam Fill material applied within annulus flush with one surface of the wall. Min fill material thickness for 1 hr F
and T Ratings is 121 mm (4-3/4 in.). Min fill material thickness for 2 hr F and T Ratings is 152 mm (6 in.).
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP 660 Firestop Foam
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
A
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
F Rating - 1 and 2 Hr (See Items 1 and 2)
FT Rating - 1 and 2 Hr (See Item 2)
FH Rating - 0 Hr
FTH Rating - 0 Hr
A
1
2
CANADA ONLY
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to CAN/ULC-S115
System No. W-L-8104
SECTION B-B
WL 8104
Page: 1 of 5
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
F Ratings — 1 and 2 Hr (See Items 1, 3 and 4)
FT Ratings — 0, 1/2, 1, 1-1/2 and 2 Hr (See Item 2)
FH Rating — 0 Hr
FTH Rating — 0 Hr
Hilti Firestop Systems
CANADA ONLY
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to CAN/ULC-S115
SECTION A-A
A
A
F
C
G
C
F
G
B
B
E
E
D
D
1
2
3
2
3
4A
4B
Page: 2 of 5
Hilti Firestop Systems
System No. W-L-8104
WL 8104
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to CAN/ULC-S115
SECTION F-F
SECTION E-E
SECTION D-DSECTION C-C
2
3B
3A
1
2
3
1
2
3
4
3
2
Page: 3 of 5
Hilti Firestop Systems
System No. W-L-8104
WL 8104
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to CAN/ULC-S115
SECTION G-G
1
2
3

the individual U400, W400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction
features:


and Partition Design. Max area of opening is 2903 cm2 (450 in2) with max dimension of 762 mm (30 in.).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall asembly in which it is installed.

Unless otherwise indicated, the space between firestop configurations and periphery of opening shall be min 9.5 mm (3/8 in.). Pipe, conduit,
tubing or cables to be rigidly supported on both sides of floor or wall assembly. The T Rating of the sytem is dependent on the firestop
configurations, as shown in the table below. Any combination of the following firestop configurations detailed herein may be used:
Firestop Configuration
1 Hr F Rating
FT Rating Hr
2 Hr F Rating
FT Rating Hr
A 0 1/2
B 1 1-1/2
C 1/2 1
D 0 0
E 1 2
F 0 0
G 0 0
Page: 4 of 5
Firestop Configuration A

be any combination of the following types and sizes of cables:
A. Max 25 pair No. 24 AWG copper telephone cable with polyvinyl chloride (PVC) insulation and jacket materials.
B. Max 7/C No. 12 AWG cable with PVC insulation and jacket materials.
C. Multiple fiber optical communication cables with PVC jacket material and having a max outside diameter of 3/8 in.
D. Max 3/C No. 12 AWG steel clad cables with PVC insulation and jacket materials.
E. Max 3/C No. 8 AWG cable with ground with PVC insulation and jacket materials.
F. Max RG 59 coaxial cables with PVC insulation and jacket materials.

F Rating is 121 mm (4-3/4 in.). Min fill material thickness for 2 hr F Rating is 152 mm (6 in.).

Firestop Configuration B

copper pipe. Min space between adjacent penetrants shall be 76 mm (3 in.).

tubing. The min space between adjacent penetrants shall be 38 mm (1-1/2 in.).
See Plastics+ (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component tube
insulation material meeting the above specifications and having a UL 94 Flammability Classificationof 94-5VA may be used.


continuously wrapped around the outer circumference of the pipe covering one time and held in place with tape. Wrap strips are installed flush
with each side of wall.


1 hr F Rating is 121 mm (4-3/4 in.). Min fill material thickness for 2 hr F Rating is 152 mm (6 in.).

Firestop Configuration C

supply) or vented (drain, waste or vent) piping system. The min space between non-metallic penetrants shall be 25 mm (1 in.). The min space
between metallic penetrants shall be 89 mm (3-1/2 in.).


continuously wrapped around the outer circumference of the pipe covering one time and held in place with tape. Wrap strips are installed flush
with each side of wall.


1 hr F Rating is 121 mm (4-3/4 in.). Min fill material thickness for 2 hr F Rating is 152 mm (6 in.).

Hilti Firestop Systems
System No. W-L-8104
WL 8104
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to CAN/ULC-S115
Page: 5 of 5
Firestop Configuration D

annular space between the pipe, conduit or tube and the periphery of the opening shall be min. 0 mm (point contact). The annular space between
adjacent penetrants shall be min 89 mm (3-1/2 in.) The following types and sizes of metallic pipes, conduits or tubes may be used:







Rating is 121 mm (4-3/4 in.) Min fill material thickness for 2 hr F Rating is 152 mm (6 in.).

Firestop Configuration E


with an all-service jacket. Longitudinal joints sealed with metal fasteners or factory-applied, self-sealing lap tape. Transverse joints secured with
metal fasteners of with butt tape supplied with product. The min space between adjacent penetrants shall be 51 mm (2 in.).
See Pipe and Equipment Covering - Materials (BRGU) Category in the Building Materials Directory for names of manufacturers. Any pipe covering
meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke Developed
Index of 50 or less may be used.

F Rating is 121 mm (4-3/4 in.). Min fill material thickness for 2 hr F Rating is 152 mm (6 in.).

Firestop Configuration F

in.).

F Rating is 121 mm (4-3/4 in.). Min fill material thickness for 2 hr F Rating is 152 mm (6 in.).

Firestop Configuration G

be 38 mm (1-1/2 in.).

Rating is 121 mm (4-3/4 in.). Min fill material thickness for 2 hr F Rating is 152 mm (6 in.).

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
Hilti Firestop Systems
System No. W-L-8104
WL 8104
Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
January 25, 2016
C
C
L
A
S
S
I
F
I
E
D
Classified by
Underwriters Laboratories, Inc.
to CAN/ULC-S115
Hilti Firestop
Saving lives
through innovation
and education
Product Information
Hilti. Outperform. Outlast.
Hilti (Canada) Corp. 1-800-363-4458 • www.hilti.ca • Hilti Firestop Systems Guide — Canada
Firestop Block
(CFS-BL)
Product description
Ready-to-use, intumescent exible block designed to seal medium
to large size openings
Product features
Integrated “Grid-Tech” increases Annular Space up to 12”
Suitable for re-penetration or new penetrations
Economical to use with short installation times
Easy installation — no special tools required
Ideal for use in oors — no forming required
One sided wall systems available
Halogen, asbestos and solvent free
Operational immediately after installation
Smoke resistant
Areas of application
Sealing single or multiple penetrations in small to large openings
Temporary or permanent sealing of cables and cable tray
penetrations
Temporary or permanent sealing of insulated and non-insulated
metallic pipes and combustible pipe penetrations
For use with
Walls (UL tested up to max. opening 72" x 36")
Floors (UL tested up to max. opening 72" x 36")
Concrete, porous concrete, masonry and gypsum wall assemblies
Wall assemblies rated up to 4 hours
Floor assemblies rated up to 3 hours
Examples
Completely dust and ber free rooms and places where electrical
installations are frequently used (ie: computer centers, hospitals,
laboratories, etc.)
New buildings in the construction phase and during renovation
Large openings containing multiple penetrations as found in
production bays, warehouses, hospitals etc.
Installation instructions for Firestop Block CFS-BL
FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-
PENETRATION FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
R
FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
Notice
Before handling, read Material Safety Data Sheet and
product label for safe usage and health information.
Instructions below are general guidelines — always
refer to the applicable drawing in the UL Fire
Resistance Directory or Hilti Firestop Systems Guide
for complete installation information
Opening
1. Clean the opening. Penetration and penetration
supporting structures must be installed in
compliance with local building and electrical
standards.
Application of Firestop Blocks
2a.If no penetrations are located, build up Firestop
Block CFS-BL, firmly seated, within opening.
2b.If penetrations are located, build up Firestop Block
CFS-BL, firmly seated, while cutting blocks with a
knife to suit the placed penetrations.
3. Finish building up Firestop Blocks until entire
opening is filled.
4. Completely fill cable spaces, gaps between blocks
and pipes, and joints with FS-ONE Firestop Sealant
(as required).
5. For maintenance reasons, a penetration seal could
be permanently marked with an identification plate.
In such a case, mark the identification plate and
fasten it in a visible position next to the seal.
Re-installing cables or other penetrations
Remove or cut the block from the seal.
Install the penetrant and re-lay the block in
compliance with the approval. Fill gaps and spaces
with FS-ONE Firestop Sealant (as required).
Single cables can be run through joints between
blocks or a hole can be drilled through a block using
a sharpened piece of metal pipe or tubing.
Not for use
In wet rooms, outdoors or exposed to the weather
or UV radiation (can be done only after applying an
additional silicone coating, i.e. CP 601S).
Storage
Store only in the original packaging in a location
protected from moisture and direct sunlight
1. Clean opening. 2a. Build up blocks 2b. Cut blocks to
size for penetrations
in place
3. Build up blocks 4. Fill gaps with
FS-ONE, CP 617
or CP 618 putty (as
required).
5. Fasten identication
plate in place (If
required)
Technical Data* CFS-BL
Color
Red
Application temperature
40° F to 104° F (5° C to 40° C)
Temperature resistance
5° F to 140° F (-15° C to 60° C)
Intumescent activation
Approx. 392° F (200° C)
Expansion ratio (unrestricted)
Up to 1:3
Surface burning characteristics
(ASTM E 84-10b)
Flame Spread Index: 10
Smoke Development Index: 15
Sound transmission classication
(ASTM E 90)
STC Rating: 52
Tested in accordance with
• UL 1479 • ASTM E 814 • ASTM E 84 • CAN/ULC-S115
*At 73°F (23°C) and 50% relative humidity
NEW
Grid-Tech!
Issued to:
Hilti Construction Chemicals, Div of Hilti Inc.
5400 S 122
East Ave
Tulsa, OK 74146
This is to certify that
representative samples of
Fill, Void or Cavity Materials
CFS-BL Firestop Block
Have been investigated by Underwriters Laboratories in accordance with
the Standard(s) indicated on this Certificate.
Standard(s) for Safety:
ANSI/UL 1479, "Fire Tests of Through-Penetration Firestops,"
CAN/ULC-S115, "Standard Method of Fire Tests of Firestop Systems."
Third Edition revised March 1, 2010
Additional Information:
See UL On-line Certification Directory at WWW.UL.COM for additional information.
CFS-BL Firestop Block for use in Through-Penetration Firestop Systems as currently described in the
UL Fire Resistance Directory.
Hilti, Inc.
5400 South 122
nd
East Avenue
Tulsa, OK 74146
1-800-879-8000
www.hilti.com
September 24, 2015
To Whom It May Concern:
Re: Hilti CFS-BL, Firestop Block – LEED Info.
Item Number:
2030020
The CFS-BL is manufactured in Kaufering, Germany.
There is no post-consumer or post-industrial content in CFS-BL and it cannot be recycled. The CFS-BL does not contain any
Rapidly Renewable Materials. The VOC content for CFS-BL is 5.4 grams/liter.
CFS-BL is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated
industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state
regulatory agencies for direction on disposal.
Please feel free to contact me at (918) 872-3704 if you have questions.
Sincerely,
Jerry Metcalf MPH, CHMM
Sr. Mgr. Safety/Environmental
Hilti Inc.
918 872 3704
Rev. Date: 9/24/15
The manufacturing plant location on this certificate has been provided for LEEDS reporting purposes only. It should never be used
for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America
requirements, as those requirements differ.
The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. “Specially” produced
non-catalog Hilti products may have differing manufacturing plant locations.
Contact your Hilti representative in cases of “specially” produced products for a custom LEEDS certificates
Hilti Firestop
Saving lives
through innovation
and education
Product Information
Hilti. Outperform. Outlast.
Hilti (Canada) Corp. 1-800-363-4458 • www.hilti.ca • Hilti Firestop Systems Guide — Canada
Introduction Applications and Products Selector Guide Through-Penetration Joint Reference Data
Firestop Wrap Strip
(CP 648-E)
Product description
An intumescent, exible restop wrap strip for plastic and
insulated pipe penetrations
Product features
Highly Intumescent
Long length avoids waste
Can be continuously wrapped
Cost effective
Quick and easy closure without tools
Ideal for very tight installations
Areas of application
Firestopping combustible pipe penetrations
Difcult applications where space is limited
Penetrations through concrete over metal deck
Plastic and insulated penetrations using
PVC, CPVC, ABS, FRPP and PEX
For use with
Concrete, masonry, wood oor and gypsum wall assemblies
Wall and oor assemblies rated up to 4 hours
Examples
Waste water pipes
Fresh water pipes
Decking penetrations
Technical Data* CP 648-E
Density
Approx. 1.35 g/cm
3
Dimensions (approximate)
3/16" x 1" x 33 ft or
3/16" x 1-3/4" x 33 ft
Color
Black with foil backing
Temperature resistance
–40°F to 212°F (–40°C to 100°C)
Intumescent activation
Approx. 320°F (160°C)
Expansion ratio (unrestricted)
1:40
Tested in accordance with
• UL 1479 • ASTM E 814 • ASTM G21 • CAN/ULC-S115
*At 73°F (23°C) and 50% relative humidity
Installation instructions for CP 648-E
sodfm,ev iJdjfiwhriuh. N|oWE
Z8Z23aw|p3i4e0288u27Āuze
4i5kirdwiloi4jtf-|x-.vbvbvh, ireiv
u9+
12oeoo
CP 648 Brandschutzmansch.
Notice
Before handling, read Material Safety Data Sheet and
product label for safe usage and health information.
Instructions below are general guidelines — always
refer to the applicable drawing in the UL Fire
Resistance Directory or Hilti Firestop Systems Guide
for complete installation information
Opening
1. Clean the plastic or insulated pipe penetration.
Expansion of the intumescent material during a fire
closes the plastic or insulated pipe penetration. Very
dirty pipes (ie: with remains of mortar) may lead to
a delay in this closing action. Soiled plastic pipes
or insulated pipe penetrations should, therefore, be
cleaned in the area where the CP 648-E Firestop
Wrap Strip is to be installed.
Application of firestop system
2. Tightly wrap the required number of strips
continuously around the penetrant, and hold in place
with tape.
3. Push the Hilti Wrap Strip into the opening until it is
flush with the substrate surface unless otherwise
required by the UL system. It may be required by
the UL system to clamp, wire or use a Hilti Retaining
Collar to secure the wrap strip in place for some
applications.
4. If the UL system requires a cold smoke seal, then
apply the proper amount of Hilti FS-ONE sealant in
the opening over the wrap strip.
5. For maintenance reasons, a penetration seal can be
permanently marked with an identification plate and
fastened in a visible position next to the seal.
Not for use
In highly corrosive surroundings
With unapproved retaining collars, anchors/fasteners
Outdoors
Storage
Store only in the original packaging in a location
protected from moisture at temperatures between
23°F and 86°F (–5°C and 30°C).
FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
FM
$33529('
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
R
FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
66Y7
1. Clean penetration 2. Wrap strips around
pipe the specied number
of times
3. Push Wrap Strips
into hole
4. Seal penetration against
smoke with FS-ONE
5. Fasten installation plate
(If required)
Firestop
System
Visit fbcsystemcompatible.com.
FBC™ is a trademark of
the Lubrizol Corporation.
CERTIFICATE OF COMPLIANCE
Certificate Numbe
r
20160829-R13240
Report Reference
R13240
Issue Date
2016-August-29
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 1
Issued to:
Hilti Construction Chemicals, Div of Hilti Inc.
5400 S 122
nd
East Ave
Tulsa, OK 74146
This is to certify that
representative samples o
f
Fill, Void or Cavity Materials
Fill, Void or Cavity Materials Certified for Canada
CP 648E and CP 648S (Product number may be suffixed to
denote size) Wrap Strip for use in Through-Penetration
Firestop Firestop Systems as currently decribed in the UL
Fire Resistance Directory and in the Products Certified for
Canada Directory.
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety:
ANSI/UL 1479, "Fire Tests of Through-Penetration
Firestops,"
CAN/ULC-S115, "Standard Method of Fire Tests of Firestop
Systems."
Additional Information:
See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.
Hilti, Inc.
5400 South 122
nd
East Avenue
Tulsa, OK 74146
1-800-879-8000
www.hilti.com
September 24, 2015
To Whom It May Concern:
Re: CP 648 E&S Firestop Wrap Strips – LEED Information
Item Numbers:
304303
304304
304305
304306
304307
304308
304309
The Hilti CP 648 E & S Firestop Wrap Strips are manufactured in Germany.
The Hilti CP 648 E & S Firestop Wrap Strips have a VOC content of 3.1 grams/liter.
The amount of post-consumer or post-industrial content in CP 648 E & S Firestop Wrap Strips is not known. The packaging is
recyclable. The CP 648 E & S Firestop Wrap Strips do not contain any Rapidly Renewable Materials.
The CP 648 E & S Firestop Wrap Strips are not regulated as a hazardous waste by the Federal EPA Standards. The regulations
for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should
consult your local and state regulatory agencies for direction on disposal.
Please feel free to contact me at (918) 872-3704 if you have questions.
Sincerely,
Jerry Metcalf MPH, CHMM
Sr. Manager, Safety/Environmental
Hilti Inc.
(918) 872 3704
Rev. Date: 8/14/15
The manufacturing plant location on this certificate has been provided for LEEDS reporting purposes only. It should never be used
for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America
requirements, as those requirements differ.
The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. “Specially” produced
non-catalog Hilti products may have differing manufacturing plant locations.
Contact your Hilti representative in cases of “specially” produced products for a custom LEEDS certificates.
CERTIFICATE OF COMPLIANCE
Certificate Numbe
r
20160125-R13240
Report Reference
R13240-20160123
Issue Date
2016-JANUARY-25
Bruce Mahrenholz, Director North American Certification Program
UL LLC
Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/
Page 1 of 1
Issued to:
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC
5400 S 122ND EAST AVE
TULSA OK 74146
This is to certify that
representative samples o
f
FILL, VOID OR CAVITY MATERIALS
The product covered by this Section of the Procedure is a
two component polyurethane foam Fill, Void or Cavity
Material designated as CP 660 Firestop Foam for use in
Through-Penetration Firestop Systems. The “B”
component, a blended product, is used as received from a
supplier. The “A” component is blended internally.
Have been investigated by UL in accordance with the
Standard(s) indicated on this Certificate.
Standard(s) for Safety:
ANSI/UL 1479-Fire Tests of Through-Penetration
Firestops,CAN/ULC-S115-Method of Fire Tests of Firestops
Systems
Additional Information:
See the UL Online Certifications Directory at
www.ul.com/database for additional information
Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.
Look for the UL Certification Mark on the product.