page 1 of 1Hilti Firestop Intumescent Sealant | Issue May 2014
www.hilti.com.au | T 131 292
Instructions for use
Hilti Firestop
Intumescent Sealant
Installation instructions
FIRESTOP APPROVAL NOTES:
1: RIR = Regulatory Information Report, which relates to Australian Standards:
Fire Tests in accordance with AS 1530.4-2005
Assessments in accordance with AS 4072.1-2005
2: RIR # 27912900 : Version 0.2 : Issued on 14 / 04 / 2014
Clean the opening to be sealed. The material around the opening must be dry,
in sound condition and free from dust or grease.
Pack mineral wool. Leave sufcient depth for applying
Hilti Firestop Intumescent Sealant CP 611A..
Apply CP 611A. Apply to the required depth in order to obtain the desired re rating.
Making sure CFS-IS contacts all surfaces to provide maximum adhesion.
Smooth CP 611A. Smooth before the skin forms using water and a spatula.
Leave completed seal undisturbed for 48 hours.
For maintenance reasons, a penetration seal could be permanently marked
with an installation plate.
For special seal types with additional Hilti Firestop Intumescent Sealant
CP 611A along the cables/conduits see RIR.