Thermafiber
®
Safing
TM
Insulation
Description:
Thermafiber
®
Insolutions
®
:
For Further Information:
Notice:
Submittal Approvals:
THERMAFIBER Safing
TM
products are designed to provide life saving fire protection in perimeter fire containment
systems, floor and wall penetrations, construction joints, and other firestopping applications. These products are
noncombustible, moisture-resistant, noncorrosive, nondeteriorating, mildew-proof and vermin-proof. Thermafiber Safing
provides thermal insulation, fire protection, and acoustical control in many different UL and Intertek (formerly OPL) listed
fire containment assemblies of 1, 2, and 3-hr ratings.
Thermafiber offers industry leading technical and engineering assistance to architects, specifiers, and contractors.
These services include CAD drawings, engineering judgments, LEED® Credit Information, product recommendations,
and customized products. Contact our technical services department at
For additional information about these or other Thermafiber products contact us at 1-888-834-2371 or visit our
website www.thermafiber.com.
THERMAFIBER, Inc. shall not be liable for incidental and consequential damages, directly or indirectly sustained, nor for any loss caused by application of
these goods not in accordance with current printed instructions or for other than the intended use. THERMAFIBER liability is expressly limited to replacement of
defective goods. Any claim shall be deemed waived unless made in writing within thirty (30) days from date it was or reasonably should have been discovered.
Job Name
Contractor
Date
3711 Mill Street | Wabash, IN 46992 | 888-TFIBER1 [834-2371] | [260] 563-2111 | www.thermafiber.com
Standard Sizes:
Standards Compliance:
Safing
TM
Insulation meets the following:
ASTM C 665 Non-corrosive, Type I, III
ASTM C 612 Type IA, IB, II
ASTM E 136 Rated Non-combustible per NFPA Standard 220
CAN/ULC S114 Complies
ASTM E 96 Unfaced, 50 Perms as tested
ASTM E 96 Foil Faced, 0.02 Perms as tested
ASTM C 1104 Absorbs less than 1% by volume
CAN/ULC S102 Flame Spread 0, Smoke Developed 0
ASTM E 814 or UL 1479
Safing Insulation used in conjunction with an approved fill, void, or cavity material
sealant or other approved material in through – penetration firestop systems - Complies
UL 2079 Safing Insulation used in conjunction with an approved fill, void or cavity material
in construction joint systems - Complies
CAN/ULC S115 Complies
Safing products are approved by: New York City Board of Standards & Appeals – (under BSA 39-74-SM & accepted by
MEA-209-82-M, Vol. 4).
Thickness* Widths** Lengths**
Safing 4.0 pcf 1”- 7” 16”, 24”, 36” 48”, 60”
Safing 6.0 pcf 1”- 7” 16”, 24”, 36” 48”, 60”
Tolerances +1/4” - 1/8” ±1/8” ±1/2”
*Thicknesses are available in ½” increments. **Custom sizes are available upon request.
Product Options:
• Safing 4.0 pcf, 2” or greater thickness, is available with or without a vapor retarding foil facing.
• Safing 6.0 pcf, 1.5” or greater thickness, is available with or without a vapor retarding foil facing.
• Recycled Content Options
1
:
EPA Choice Fiber (US Government Buildings) ........ Minimum 75%
Standard Fiber .................................................................... 70%
1
Recycled content options other than Standard must be specified at time of order.
Installation:
All firestopping insulation should be installed per the architectural specification or system specific test description. All
compressed Safing insulation should be installed per the listed assembly.
• Perimeter Installation: Safing
TM
insulation should be compression fitted between the slab edge and the FireSpan
curtain wall insulation, leaving no voids.
• Penetration Application: Safing insulation should be cut slightly larger than the opening and compression fitted into the
opening, leaving no voids.
• Construction Joint Application: Safing insulation should be compression fitted into the joint opening, leaving no voids.
Technical Data:
TF612/Rev 03-15 Copyright 2015, Thermafiber, Inc. All Rights Reserved. LEED
®
is a registered trademark of U.S. Green Building Council.
Safing
TM
insulation is a critical component of any perimeter fire containment system. Thermafiber
®
has performed decades
of testing in all of the containment systems listed below. For more complete test information, see SA707, THERMAFIBER
Life-Safety Fire Containment Systems technical catalog or UL
®
and Intertek
®
(formerly OPL) Directories. For a full listing of
containment systems visit www.thermafiber.com and click on Fire Rated Assemblies. UL Reference = TYPE SAF
• Aluminum Spandrel Curtain Wall Fire Containment
• Steel Stud-Framed/Gypsum Sheathing Curtain Wall Fire Containment
• Glass Spandrel Curtain Wall Fire Containment
• Granite Spandrel Curtain Wall Fire Containment
• Precast Concrete Spandrel
Fire-Containment Tests
Per ASTM E 2307
Product Actual “k” @ 75° [24°C] “R” value per
Designation Density inch of thickness***
Safing 4.0 pcf 0.24 ‘R’= 4.2 0 0 25 0
Safing 6.0 pcf 0.24 ‘R’= 4.2 0 0 25 0
BTU.in/hr.sq. ft. °F
Tested to ASTM C 518
Tested to ASTM E 84
Unfaced Foil Faced
Flame
Spread
Flame
Spread
Smoke
Developed
Smoke
Developed
***R = thickness divided by ‘k’