This manual covers a range of
conventional fire panel and include
system design, installation and
configuration information.
The fire panels covered are
designed in accordance with the
requirements of EN54-2: 1997,
A1:2006, plus the requirements of
EN54-4: 1997, A1:2002, A2:2006.
This publication covers the
Con ven tional fire alarm pan els:
q 2 zone pan el:- 13270-02LB and
75585-02NMB
q 4 zone pan el:- 13270-04LB and
75585-04NMB
q 8 zone pan el:- 13270-08LB and
75585-08NMB
q Fire alarm re peat pan el:
13271-08LB and 75586-08NMB.
The panels are supplied without
bat ter ies.
This manual is intended
for use by installers and
commissioning engineers.
A separate Operating
instructions and Log book
has been supplied along
with this booklet which
must be forwarded on to
the End User.
4188-424 issue 6_Part 1_06-12
Data, In stal la tion and Com mis sion ing guide
Fire Con trol and Re peat pan els
(Con ven tional 2, 4 and 8 Zone panel range)
Content Page
System design ·· .....2
Cables - ····· .....4
Notes to installers .....5
Panel fixing···· .....6
Terminals ···· .....8
Controls & indicators ....9
Power up tests ·· .....10
Installed system tests ...11
Config. con sid er ations ...11
Access levels 2 · .....12
Op er at ing instructions for
Access level 2 func tions ..12
Programming Options ...14
Op er at ing instructions for
Access level 3 func tions ..14
Op er at ing in struc tions for
Ac cess level 4 func tions ..15
Fault indications · .....16
Fault find ing ··· .....17
Specification for the
Control panel··· .....20
Specification for the
Repeat panel··· .....22
Parts list ····· .....23
System design
The fire system design should be
to BS 5839:Part 1:2002 + A2:2008
Code of Practice for system
design installation and servicing.
Supplemented with customer
requirements.
Mains Supply
The control panel mains supply
must be via a fused spur unit
rated:
5A - 1 & 2 Zone panel/Repeat
panel
7A - 4 & 8 Zone panel
Standby Supply
With the recommended batteries
the control panel will provide a
standby supply under mains
failure conditions. A period of
72 hours followed by 30 minutes
of alarm load is possible and is
dependent on the system loading.
24V power supply
The power supply terminals ‘24+
and 0’ may drive external ancillary
equipment and is designed to be
used in conjunction with auxiliary
contacts and common fire and
fault outputs. The maximum
currents are 250mA (1 & 2 zone)
and 500mA (4 & 8 zone). The
supply is monitored for faulty 24V
supply level or fuse blowing.
NOTE: The use of the 24V
supply will affect the panel
standby capability.
Fire De tec tion
(Zone Cir cuits)
Each zone circuit can have up to
3.0mA load. An end-of-line
capacitor unit or bipolar capacitor
is required for zone circuit
monitoring, which must be fitted
after the last detector or manual
call point on the circuit. All
manual call points used must
have a 470 ohms series resistor.
Where a zone circuit is not being
used, the end-of-line capacitor unit
or bipolar capacitor must be fitted
across its terminals in the panel.
System design Fire Panels
2 4188-424 is sue 6_Part 1_06-12
Un-used Zone circuits must
be terminated with an
end-of-line Capacitor unit
or bipolar capacitor
End-of-line Capacitor unit
or bipolar capacitor
RED
BLACK
FIRE DETECTION (ZONE) CIRCUIT
A fire detector head may be fitted
to a diode-base for continuity when
a detector head is removed and
there can be a maximum of up to
20 diode-bases per zone circuit.
MANUAL
CALL
POINT
NOTE: Spur wiring is not permitted off zone circuits.
Zone
Circuit
Zone
Circuit
Control panel
Z1+ Z2+Z1- Z2-
BLACK
RED
FIRE
DETECTOR
Figure 1 Zone circuit - used and unused
IN
IN
1
1
7
7
6
6
5
5
4
4
3
3
2
2
OUT
OUT
IN
1
7
6
5
4
3
2
OUT
IN
1
7
6
5
4
3
2
OUT
IN
1
7
6
5
4
3
2
OUT
LED unit
Base showing
End of Line
device fitted
Base with LED
connection
Standard base shown. Diode
base connection is identical.
Standard base
MCP
Zone
Circuit
Zn+
Zn-
NOTE: LED unit is supplied
with LED module
NOTE: End of line unit
is supplied with panel
Zone
Circuit
Control panel
Zn+
Zn-
Earth continuity
+
-
Control panel
Connection to 17800 range of detector bases are shown here.
1 2 3 4
Vision detector wiring
Standard base
Figure 2 Connection to detectors, cal l points and panel
Alarm (Sounder cir cuits)
To comply with the requirements
of BS 5839: Part 1:2002 +
A2:2008, two or more alarm
sounder circuits should be used
on all installations.
NOTE: All sounder circuits
(sectors) will operate together in
the event of a fire condition.
NOTE: Each sounder output is
0.5A maximum protected by
0.75A fuse.
1 & 2 Zone
Panels
4 & 8 Zone
Panels
1A maximum
Alarm sounder
load per panel
1.5A maximum
Alarm sounder
load per panel
The load must be shared between
the sounder circuits. The alarm
sounder circuits are regularly
pulse monitored for failure. It is
important that the last alarm
sounder is fitted with a 10K Ohm
end-of-line resistor.
The sounder outputs are
monitored in alarm for loss of
supply or multiple sounder output
overloads
Where a sounder circuit is not
being used, the end-of-line resistor
must be fitted across its terminals
in the control panel.
Class Change
A pair of unmonitored ter mi nals
al low only the sys tem alarm
sound ers to be ac ti vated from a
re mote po si tion. It is con sid ered that
the ma jor use for these will be for
class change func tions in schools
and col leges.
Aux il iary Con tacts
These are normally open (NO) and
normally closed (NC) contacts that
change over when the panel goes
into a fire condition. The contacts
are rated at 24V dc 1A for a
resistive load and should not be
used to switch voltages in excess of
50V. The auxiliary circuits should be
powered from an independent
power supply.
NOTE:There is no
indication given at the
panel of class change push
button operation.
Fire Panels System design
4188-424 is sue 6_Part 1_06-12 3
NOTE: Spur wiring is not permitted
off alarm sounder circuits.
Sounder
Sounder
Control panel
Alarm sounders
must be polarised
and suppressed.
S1+
Sn+S1- Sn-
Alarm sounder
must have a
series blocking
diode
Sounder circuit that is
not used is terminated
with an end-of line resistor
ALARM SOUNDER CIRCUIT
End-of-line Resistor
10k Ohms
Control panel
Sn+
Sn-
Earth
continuity
Sounder
Figure 3 Alarm sounder circuit used and unus ed
Class change
100m max.
Cable
distance
Push button switch
or relay pulsed
at 1 second
interval (minimum)
for class change
application
CC1
CC2
Control panel
Figure 4 Class change circuit
Contacts rated 1A@24Vdc
Contacts
change
over occur
with a fire
condition
NC
NC
N0
N0
Auxiliary
contacts
Control panel
100m maximum
cable distance
Figure 5 Auxiliary contacts
Com mon Fire and fault
The common fire output is a
normally open electronic switch
that closes with a fire condition.
The common fault output is a
normally closed electronic switch,
which opens with a fault condition,
this is for a fail safe operation.
Each electronic switch is current
limited, see specification.
Use a relay to provide volt free
contacts.
The +24V & 0V is a power supply
for use with auxiliary contacts,
common fire and common fault
circuits, see specification.
Re peat Panel
A Repeat panel can be connected
in series to the control panel. A
repeat panel duplicates fire and
fault indications together with
system controls.
Cables Fire Panels
4 4188-424 is sue 6_Part 1_06-12
Figure 6 Fire
fault & 24V
outputs
Length per circuit Type of circuit Recommended cables, also see BS5839:Part 1 guidance
2m Mains power supply cord see power supply cord
1Km Zone circuit
See BS5839:Part 1:2002 + A2:2008 for guidance
1Km Sounder circuits
100m Auxiliary circuit
100m Common fire and fault circuit
100m Class change circuit
500m total circuit Repeat panel link Belden type - screened 2-core twisted pair
Cables
The guidance of
BS5839:Part 1:2002 + A2:2008,
should be followed.
Generally available electrical
installation cable may be used,
providing the cable is:
q to BS6387
q with no more than 2 - cores
q each core hav ing no less than
1.5mm
2
cross sec tion area
(max i mum 2.5mm
2
).
q with an in her ent or through
metal con duit screen for earth
con ti nu ity in or der to pro duce
elec tri cal pro tec tion and
screen ing.
q hav ing pro tec tion from heat and
me chan i cal dam age.
Power supply cord
The mains supply to the panel
should be wired in 0.75mm
2
cable
with a effective connection to
building service earth continuity
conductor.
R+
R-
Control panel
Repeat panel
Screen must be
connected to panel
R+ R-
Figure 7 Control
to repeat panel
connections
Notes to installers
Check
q The power-up and
com mis sion ing is done by the
ser vic ing or gani sa tion.
q The wires be tween the
ter mi na tion point and ter mi nals
should be short and straight
as pos si ble.
q The ca bles of the fire de tec tion
and alarm sys tem and other
sys tems should usu ally be
sep a rated by at least 160mm,
un less ded i cated con duit or
ducting is used.
q Do not use any part of build ing
struc ture for earthing.
q The ca ble length be tween the
Re peat LED unit and re spec tive
fire de tec tor where used, should
not ex ceed 10m.
q Ca ble Glands should be used
on the equip ment for the mains
sup ply ca ble.
q Un used knock outs on prod uct
en clo sure that have been
re moved, should not be left
open.
Requirements
It is recommended that the
installer follow the general
requirements of:
q BS5839:Part 1:2002 + A2:2008,
which is the code of prac tice
re lat ing to the fire de tec tion and
alarm sys tems for build ings.
q the rel e vant parts of the
BS 7671 Re quire ments for
Elec tri cal In stal la tion.
Second fix
To prevent the possibility of
damage or dirt degrading the
performance or appearance of the
System products, the installation
of second fix items should be
delayed until all major building
work in the area is complete.
Fix tures and fit tings
It is the installers responsibility to
provide:
· adequate fixtures and fittings
for the type of construction
surface onto which a product
is to be installed.
· as an aid to this decision, the
weight and overall size of
each full assembly together
with implications on cable
entries and routing should be
taken into consideration.
NOTE: All these procedures
assume that the cable, gland,
steel box (BESA box) and other
related accessories are provided
by the installer.
As fitted wiring drawings
The installer should acquire:
q site spe cific in for ma tion from
the in ter ested par ties, for de tails
on the lo ca tion of prod ucts for
in stal la tion
q the ac quired in for ma tion
to gether with this guide and the
rel e vant stan dards should be
used to as sist the work.
Earth continuity
To maintain earth continuity, the
cable screen must be continued
through each system device,
whether the earth is connected to
a device or not.
NOTE: The cable from the main
panel to repeat panels if fitted
must be a screened cable.
Refer to Figure 8.
Fire Panels Notes to installers
4188-424 is sue 6_Part 1_06-12 5
4-off earth points
Mains input terminal
block c/w mains fuse
Mains supply
to panel
13-back
13-top
cable entry points
Gland
Earth
drain
Cable
Zone Cable termination
NOTE: Repeat panel link
cable entries are located
at the opposite end to the
mains cable entries, ie on
the Right Hand Side.
Panel backbox
Electronic assembly
Figure 8 Panel cable entry and earth points
Panel fixing
a) Remove panel from its carton.
b) Store the front panel (including
the electronic assembly) and
the metal plates in a safe place
until later.
c) Check the spare parts supplied
with those listed in Table 1.
d) Remove the appropriate
knock-in on the panel case for
cable entry.
e) Hold the panel on the wall in
the desired mounting position
and mark the positions of the
fixing holes. See Figure 9 for
case fixing details.
f) Secure the panel to the wall
using suitable fixings. A top
centre keyhole fixing is
provided on the case to allow
the panel to be hooked whilst
the bottom two fixing points are
located.
NOTE: For details on flush
fixing the panel, see Figure 11.
g) Connect the mains supply
cable to the panel. The cable:
· must be fed through one of
the dedicated mains cable
entry points into the panel.
· must be via an unswitched
fused spur unit, rated 5A for
the 2 Zone Control and
Repeat panels and 7A for 4&8
Zone panels.
· The fused spur isolator cover
should be red and marked:
FIRE ALARM - DO NOT SWITCH
OFF
· The fused spur units must be
fed from a dedicated isolation
switch used for the fire alarm
system only.
h) Wire the system. With the
exception of mains cable, all
other cables should remain
unconnected at the panel. For
the unconnected cable leave
300mm tail wire length and
mark each core identifying its
final point of connection.
The system wiring can be
tested whilst not connected to
the respective terminals at
each system device.
CAUTION: DO NOT undertake
high voltage insulation tests
WITH THE CABLES
CONNECTED to their terminals.
This may damage the electronic
circuitry in the product.
I) Refit the front panel (including the
electronic assembly) into the panel
using four M3 screws and connect
the transformer cable and earth
cable, see Figure 10.
j) Attach the top and bottom metal
plates using four M3 screws, see
Figure 11.
NOTE: Each terminal in a
panel will accept a
maximum conductor size of
2.5mm
2
.
NOTE: The installation of
all outstanding parts is
usually carried out during
Commissioning of the
System.
Panel fixing Fire Panels
6 4188-424 is sue 6_Part 1_06-12
Description
For fuse location
see Figure 12
Quantity supplied with control
panel
Repeat
panel
2 zone 4 zone 8 zone
10K end-of-line resistor 2 4 8
22uF Capacitor unit 2 4 8
End of line label 4 8 16
Fuse T3.15AH250V
ceramic 20 x 5mm
(mains FS1 & battery FS2)
2 2 2 2
Fuse F500mA250V
20 x 5mm (24V FS11)
1 1 1
Battery link 1 1 1 1
Zone designation label 1 1 1 1
M3 screws 8 8 8 8
Table 1 Spare parts supplied with each panel
Dedicated mains
cable entry points
Panel size
395mm wide x 274mm high x 87mm deep
89mm 89mm
19mm
197mm
111mm
4-off
earth points
How to knock-in
a cable entry point
Knock here to open
the entry point
Panel Backbox
Figure 9 Panel fixings
Store all spare parts and loose
components including the
batteries inside the panel carton
and keep in a safe place until
required.
Fire Panels Panel fixing
4188-424 is sue 6_Part 1_06-12 7
Dedicated mains
cable entry points
4-off earth points
Red
Battery connections
Black
Fixing points for the
electronic assembly
Electronic assembly
P1
To To
Transformer Earth
T1A T1B E
Panel Backbox
Transformer
cables
to electronic
assembly
Earth connection
to the electronic
assembly
+ve
-ve
Bottom Plate (instructions printed on plate)
Ribs
NOTE: The metal plates are to be located
under the ribs on the front panel and fixed
in place using M3 screws.
Figure 10 Refitting electronic assembly
378mm wide
245mm high
60mm deep
cross section of
the wall to which
the panel is to be
flush mounted
Control or Repeat
panel
Aperture
Flush
shroud
4.5 mm
diameter holes
12 holes
Figure 11 Installing a flush shroud
Terminals
Terminals Fire Panels
8 4188-424 is sue 6_Part 1_06-12
Zones
FIRE
Faults
System
Power
Earth
Sounder
Disabled
Sound
Alarms
Silence
Alarms
1
2 3
4
5 6
7
8
9
0
v
Test
Access /
Function
1 2 3 4 5 6 7 8
Cancel
Buzzer
Reset
System
CN5 CN6 CN7 CN8 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN16 CN17 CN18 CN19 CN20 CN21 CN22 CN23 CN24 CN25 CN26 CN27 CN28CN29 CN30
F1 F2 F3 F4 F5 F6 F7 F8
F9 F10 F11
SECTOR 1 SECTOR 2 SECTOR 3 SECTOR 4 SECTOR 5 SECTOR 6 SECTOR 7 SECTOR 8BATTERIES
T1A T1B T2BT2AE NC NC NO NO Z1+ Z1- S1-S1+ Z2+ Z2- S2-S2+ Z3+ Z3- S3-S3+ Z4-Z4+ S4+ S4- Z5+ Z5- S5-S5+ Z6+ Z6- S6-S6+ Z7+ Z7- S7-S7+ Z8-Z8+ S8+ S8- CC1 CC2 24+ 0CFT CFR R+ R-
POWER 1 POWER 2
FS2 (SB)
3.15A
3.15A
3.15A
3.15A
FS3
750mA
750mA
750mA
FS11 (QB)
500mA
500mA
500mA
500mA250V
FS5
750mA
750mA
FS7
750mA
FS9
750mA
FS4
750mA
750mA
750mA
FS6
750mA
750mA
FS8
750mA
FS10
750mA
Fuse
2-Zone panel
4-Zone panel
8- Zone panel
Repeat panel
Fuse marking
SECTOR 1
SECTOR 2
SECTOR 3
SECTOR 4
SECTOR 5
SECTOR 6
SECTOR 7
SECTOR 8
BATTERIES
24V
1 8
All other fuses, ie FS1, FS2 and FS11
are 20mm x 5mm diameter
QB - Quick Blow AS - Anti-Surge
SB - Slow Blow (ie Time Delay)
Fuses
T1A
T1B
E
CFR
24+
CFT
0
CC1
CC2
R+
R-
NC
NC
NO
NO
Zn+
Zn-
To Zone and Sounder
Circuits, where `n' signifies
circuit number 1 to 8
Sn-
Sn+
Auxiliary contacts
1A at 24Vdc resistive
To transformer
Mains input
supply
Software
version
label
P1
P3 to P6
P7
Class change, connect to XEN-FFR
Common fault,
Common Fire
Repeat panel
Panel
P8
EEPROM
Protection
fitted across
pins 1 and 2
Power
Shift
Display
N
The shaded terminal blocks
are not fitted on the Repeat panel.
FS1 (SB)
3.15A
3.15A
3.15A
3.15A
T3.15AH250V
(SB) - Slow blow
ceramic
All sector outputs have resettable 0.75A fuses which do not
need replacing. The individual outputs will recover after
removing the fault. The recovery time is 30 seconds minimum
and it is recommended that the sectors be switched off (Silence Alarms).
Delay
L
Product No: 13270 MAIN PANEL
Rated Voltage: 230V A.C.
Rated Current: 0.3A
Rated Frequency: 50Hz
Mains Fuse: FS1 T3.15AH250V
Manufacture date: xx/xx/xx
by Honeywell
CAUTION
HAZARDOUS VOLTAGES REMAIN
AFTER OPERATION OF FUSE
MAINS
Figure 12 Panel terminals and fuses
Controls & indicators
Nu meric key pad. Al lows the en try
of nu meric data.
q Shift key. The Shift/Function
key gives ac cess to the main
func tions of the panel.
q Dis play test key. Pressing the
Dis play Test key af ter en ter ing
ac cess code# will ini ti ate a
se quence which il lu mi nates all
the in di ca tors in turn en abling
them to be checked.
# Coded en try is only
re quired if Can cel Buzzer and
Dis play Test func tions are
con fig ured for op er a tion at
Ac cess level 2.
q Can cel Buzzer. Pressing the
Can cel Buzzer but ton af ter
en ter ing ac cess code# will stop
the in ter nal buzzer sound ing.
q Sys tem Re set. The sys tem
re set key when pressed af ter
en ter ing ac cess code will re turn
the sys tem to its nor mal
op er at ing state. If there are
uncleared fires or faults then
these con di tions will re-occur.
q Sound Alarms. Press ing the
Sound Alarms but ton af ter
en ter ing ac cess code will sound
all of the sys tem alarms. Should
only be pressed in an
emer gency or at other agreed
times, ie for sounder tests etc.
Press ing the sound alarms
but ton does not ac tion the
aux il iary re lay.
q Si lence Alarms. Pressing the
Si lence Alarms but ton af ter
en ter ing ac cess code will
si lence the sys tem alarms.
Should only be pressed when
the emer gency is over.
In di ca tors.
q Fire. When lit in di cates that the
sys tem has de tected a fire.
q Fault. When lit or flash ing
in di cates that there is a fault
con di tion on the sys tem which
re quires rec ti fi ca tion.
q Zone Fire/Fault/Disablement.
Red indicator illuminates when
there is a zone fire, it can be a
steady or flash ing indication.
For a zone fault the yel low
in di ca tor is flash ing. A lit zone
yel low in di ca tor along with the
Disabled indicator is used to
show a dis abled zone.
q Sys tem Fault. This in di ca tor
when lit in di cates that there is a
fault in the panel’s pro ces sor.
q Power Fault. When lit or flash ing
in di cates that there is a power
sup ply fault pres ent.
q Earth Fault. This in di ca tor when
lit or flash ing in di cates that there
is an Earth Fault on the sys tem.
q Sounder Fault. When flash ing in
con junc tion with a flash ing fault
in di ca tor in di cates a sounder
fault. When lit in con junc tion with
the dis abled in di ca tor in di cates
that the sound ers are dis abled.
q Dis abled. Illuminates along with
the sounder or the zone
in di ca tors to show a dis abled
con di tion.
q Test. When lit in di cates that the
panel is in Test mode.
q Power. When lit in di cates that
the panel is pow ered up.
q De lay. When lit it in di cates that a
de lay will be ef fec tive af ter
de tec tion of a fire be fore
ac ti va tion of sys tem alarms.
q Ac cess/Func tion. The
Ac cess/Func tion lamp will flash
when the shift key is pressed
and will be lit when the coded
func tions are ac cessed.
Fire Panels Controls & indicators
4188-424 is sue 6_Part 1_06-12 9
Cancel
Buzzer
System
Reset
Sound
Alarms
Silence
Alarms
1
2 3
4
5 6
7
8
9
0
v
Shift or Function
key
Shift
Numeric
keypad
Display test
key
Display
Essential controls
Zones
FIRE
Fault
System
Power
Earth
Sounder
Disabled
Test
Delay
Access /
Function
Normally lit
to indicate
Power supply
healthy
The light is lit when
the Shift/Function key is pressed
or there is an entry to controls
with coded access
ZONE Fire, Fault or Disablement indications
Other Fault
indications
1red
yellow
2 3 4 5 6 7
yellow
yellow
yellow
green
8
Power
yellow
Figure 13 Controls and indications
CONTROLS - only avail able when an ac cess code is en tered.
Power up tests
Connecting the battery will not
power up the panel, power up will
occur after mains is applied.
The total system should be tested
in accordance with the
commissioning requirements of
BS5839:Part 1:2002 + A2:2008 or
other standard specified by the
system purchaser.
NOTE: The commissioning
procedures assume that the
system has been installed as
per instructions in this booklet.
Checks before power up
q Ensure you have 'as fit ted
draw ings'
q check the sys tem has been
in stalled to the pro ject
re quire ments.
q if necessary, ac tion the in staller
to carry out rectification work.
q Remove the EEPROM
protection link from connector
P8, see Figure 14.
Initial power up
a) Disconnect cables to terminals
of zone, sounder, class
change, auxiliary, common fire
and fault circuits. Ensure each
cable is marked for
reconnection to respective
terminals later.
b) Connect end-of-line capacitor
units to zones and end-of-line
resistor units to sounder
circuits for initial power up.
c) Check mains connection and
switch on the mains power to
the control panel.
d) Now connect the battery
supply, see Figure 14.
e) Check the panel provides a
normal healthy indication, with
the green light lit.
Zone circuit tests
a) Transfer the end-of-line
capacitor unit to the last device
(detector or manual call point)
on a zone circuit.
b) Connect a zone cable to the
terminals of a zone circuit.
c) Carry out zone open circuit and
short circuit tests and check
appropriate indications are
given.
d) Repeat the above for other
zone circuits.
Sounder circuit tests
a) Transfer the end-of-line
resistor unit to the last device
on a sounder circuit.
b) Connect a sounder circuit
cable to a sounder circuit
terminals.
c) Carry out sounder open and
short circuit tests and check
appropriate indications are
given.
d) Repeat the above for other
sounder circuits.
EEPROM Protection link
NOTE: Ensure that at the end
of Commissioning and System
tests the EEPROM protection
link is fitted to connector P8,
see Figure 14.
Power up tests Fire Panels
10 4188-424 is sue 6_Part 1_06-12
+
-
Control panel
NOTE: A label is supplied in the spares pack
which can be located on this cover to identify
zone location
Connection for 12V 2.1Ah Batteries
For 1, 2 and 4 zone panels + repeat panel
a) Open the
lower outer cover
b) Remove the
lower inner plate
Instructions + Zone designation
c) Fit the batteries and
connect the battery cables
+
-
Connection for 12V 3.4Ah Batteries
For 8 zone panels
+
-
+
-
Zones
FIRE
Faults
System
Power
Earth
Sounder
Disabled
Sound
Alarms
Silence
Alarms
1
2 3
4
5 6
7
8
9
0
v
Test
Access /
Function
1 2 3 4 5 6 7 8
Cancel
Buzzer
Reset
System
Power
Shift
Display
Day/Night
1 8
P8
EEPROM
Protection
fitted across
pins 1 and 2
Figure 14 Battery installation and EEPROM protection link
Installed system tests
The fire detection and alarm
system should be tested to ensure
it operates to meet the standards
and project requirements.
Configuration
The control panel is factory set to
the requirements of EN54 Parts 2
and 4.
With Test mode A or B active: a
triggered manual call point or fire
detector in the test zone will give:
The operation of the control and
repeat panels and the system may
be re-configured to site specific
needs.
To facilitate tests on the fire
detection and alarm system the
control panel can be set to operate
in a test mode. Note a detector
that is still full of smoke or heat will
retrigger into a fire condition until
the smoke or heat in the area is
cleared.
Sound level test
Sound level tests should be
conducted to standard
requirements and to customer
satisfaction.
Other equipment tests
Where external equipment is
connected to the control panel
using auxiliary, common fire and
fault terminals, then these must be
tested to project requirements.
Zone designation label
a) Write on to the zone
designation label the name that
identifies the area protected by
each zone circuit.
b) Fix the label over the zone
designation part of the lower
inner plate, see Figure 14.
Log book
Fill in the system details on the
first three pages of the log book.
On completion
Ensure the persons responsible
for the system are made aware of:
- system operation
- access codes to controls
- basic controls
- their responsibility
- and the need to log system
events in the log book.
Fire Panels Installed system tests
4188-424 is sue 6_Part 1_06-12 11
Test A
Fire indication for
10 seconds duration
followed by a system
reset
Test B
System alarm sounds for
the first 2 seconds and
at the same time a Fire
indication is given for
10 seconds duration
followed by a system
reset
Table 2 Test mode operation
Config. con sid er ations
Re peat panel config.
q The power up pro ce dure for the
re peat panel is the same as the
main panel.
q The pres ence of a re peat panel
needs to be set up at the main
panel, see Config. and Test
sec tion.
De lay mode
In the Delay mode there is a delay
between detecting a fire and
sounding the alarms to enable the
fire to be investigated. The panel
will upon detection of a fire:
q Il lu mi nate the Com mon fire and
ap pro pri ate zone fire lamps.
q Cause the pan els in ter nal
buzzer to emit the fire tone.
q Ac ti vate the com mon fire and
aux il iary out puts.
q De lays the ac ti va tion of the
sound ers for a configurable
de lay of be tween 1 and 10
min utes in 1 min ute steps.
If the panel is reset during the
delay period, the delay is
cancelled. Also if another fire
occurs in a different zone to the
first fire, the alarms will activate
immediately. You can override the
delay and activate all sounders in
the system by operating the Sound
Alarms button.
False alarm re jec tion
q This is an en hanced fire
alarm rejection al go rithm
de signed to give greater
im mu nity to spu ri ous alarms.
q The Fire alarm rejection
al go rithm should only be used in
con junc tion with rec om mended
de tec tors to guar an tee that the
sys tem will re ject spu ri ous events
but will de tect and an nun ci ate
real fires within 10 sec onds,
which is an EN54-part 2
re quire ment. When set, the
al go rithm ap plies to ALL zones
on the panel.
Visual indications Signals out
Condition Zone
Fire
(1-8)
-Red
Zone
Fault
(1-8) -
Yellow
Test -
Yellow
Power -
Green
Access/
Function
- Yellow
Aux Relay contacts
Normally de-
energised
Common fault -
Normally active
Common fire-
Normally deactive
Test A or B
(Normal)
On On On On Normal Active Deactive
Test A
(Fire)
On On On On Normal Active Deactive
Test B
(Fire)
On On On On Normal Active Deactive
Test condition indications
Access levels 2
To configure the system enter the
appropriate access code.
NOTE: It is only necessary to
enter the access code once,
provided the 2 minute timeout is
not exceeded between button
presses.
Access codes
Factory set codes are:
Access level 2 Code : 123
Depending on how the system is
configured coded entry may be
necessary for test.
The factory codes can be
changed at any time after power
up.
NOTE: It is important to leave
the system in a normal
operating condition on
completion of commissioning.
NOTE: The auxiliary contacts do
not operate in the Test Modes.
Access levels 2 Fire Panels
12 4188-424 is sue 6_Part 1_06-12
Operating Instructions for AL2 functions
How to do a Display test
q Enter the AL2 ac cess code and check that the Access/function lamp is lit.
q Press the shift and dis play but tons and check that all indicators are lit.
How to set the panel to operate in Test mode A
q En ter the AL2 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 3 but tons fol lowed by the num ber of the zone to be placed in test mode.
- Check that the Test indicator is On and the zone fault indicator is lit.
- The zone can be tested without an alarm of fire
How to set the panel to operate in Test mode B
q En ter the AL2 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 4 but tons fol lowed by the num ber of the zone to be placed in test mode.
- Check that the Test indicator is On and the zone fault indicator is lit.
- The zone can be tested with 2 seconds alarm of fire.
How to cancel Test mode A/B
q En ter the AL2 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 5 but tons fol lowed by the num ber of the zone to have test mode cleared.
- The test mode A or B is cancelled.
How to disable a zone
q En ter the AL2 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 1 but tons fol lowed by the num ber of the zone to be dis abled.
- Check that the appropriate Zone fault indicator and the Disabled indicator are lit.
- A detected fire in the disabled zone will not cause the panel to go into fire condition.
How to enable a zone
q En ter the AL2 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 2 but tons fol lowed by the num ber of the zone to be re-enabled.
- The previously disabled zone is re-enabled.
Fire Panels Operating Instructions for AL2 functions
4188-424 is sue 6_Part 1_06-12 13
How to disable sounders
q En ter the AL2 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 1 but tons fol lowed by 0.
- Check that the Sounder and Disabled indicators are lit.
- The Sounder circuits are disabled.
How to enable sounders
q En ter the AL2 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 2 but tons fol lowed by 0.
- The previously disabled sounders are now re-enabled.
How to change AL2 password
q En ter the AL3 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 9001 but tons in se quence and check that the System LED is flashing
q In put the new AL2 ac cess code.
How to change AL3 password
q En ter the AL3 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 9002 but tons in se quence and check that the System LED is flashing
q In put the new AL3 ac cess code.
How to set and unset the Delay mode
q En ter the AL2 ac cess code and check that the Access/function lamp is lit.
q Press the shift and 6 but tons.
- The Delay mode toggles between Delay and No Delay each time this operation is performed.
When Delay mode is selected the Delay lamp is lit.
How to exit from AL2, AL3 or AL4 to AL1
q Press the shift but ton fol lowed by 0.
- Check that the Access/function lamp is extinguished.
- The panel is now in access level AL1.
Programming Options
NOTE: There is a 2 minute
timeout on the access levels. If
this period is exceeded the
code will have to be re-entered.
In order to access the EEPROM,
the EEPROM protection link
needs removing, see Figure 14.
The default settings of the panel
may be changed to suit site
requirements.
Factory set codes:
AL3 code is: 321
This is the code on first power-up
and it can be changed at any time.
AL4 code is: 7426
This code is for the use by the
servicing organisation only.
There is a reset code, 2623
which will reset the AL2 and AL3
codes to their factory settings.
Whilst the EEPROM is
unprotected during programming,
the system fault light will flash to
indicate that the EEPROM
protection link is removed. If
further changes are required, the
sequence shift followed by 9000
must be re-entered.
Once the changes have been
made, the panel must be powered
down and then powered up again
for the changes to take place.
NOTE: After programming is
complete the EEPROM
protection link must be refitted.
Programming Options Fire Panels
14 4188-424 is sue 6_Part 1_06-12
Op er at ing instructions for Access level 3 func tions
To allow Can cel buzzer at ac cess level 1 (de fault set ting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 000 000
To allow Can cel buzzer at ac cess level 2
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 000 001
To allow Dis play test at ac cess level 1
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 001 001
To allow Dis play test at ac cess level 2 (de fault set ting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 001 002
To allow Test con di tion at ac cess level 2 (de fault set ting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 002 002
To allow Test con di tion at ac cess level 3
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 002 003
To allow most re cent alarm in di ca tion as a steady state in di ca tion (de fault set ting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 003 000
To allow most re cent alarm as a puls ing in di ca tion
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 003 001
To allow Aux il iary out put to activate in fire and de ac ti vate on re set (de fault set ting)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 005 000
To allow Aux il iary out put to activate in fire and de ac ti vate on re set and si lence alarms
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 005 001
To change the De lay mode set ting (de fault set ting is 1 min ute)
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 006 and data 000 to 010 in
minutes. Note if a value of greater than 10 minutes is entered, it will be truncated to 10 minutes.
Fire Panels Op er at ing in struc tions for Ac cess level 4 func tions
4188-424 is sue 6_Part 1_06-12 15
To allow False Alarm Re jec tion On/Off (de fault is Off)
q Enter 3 digit AL3 code (default = 321), press shift, Enter 9000 007 followed by 000 to turn the false alarm
rejection algorithm Off.
q Enter 3 digit AL3 code (default = 321), press shift, Enter 9000 007 followed by 001 to turn the false alarm
rejection algorithm On.
To enter num ber of connected Re peat panels (de fault set ting is 0) - TO BE SET AT MAIN PANEL
q Enter 3 digit AL3 access code (default = 321), Press Shift, Enter data 9000 009 001
Op er at ing in struc tions for Ac cess level 4 func tions
CAUTION: These AL4 functions are for trained engineers only and normally
access to these functions is NOT required.
How to set Non Latching Zone con fig u ra tion (de fault set ting is all zones are latch ing)
q A non latching zone fire condition will not action the auxiliary relay.
Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 032 and data as follows:
Decimal equivalent of eight bit number where a ‘1’ signifies a latching zone and a ‘0’ signifies a non latching
zone, also bit 0 corresponds to zone 1 and bit 7 corresponds to zone 8.
E.g. Requirement eight bit number data
All Zones non latching 00000000 000
Zone 1 latching, all others non latching 00000001 001
Zones 3,5,6 latching, all others non latching 00110100 052
All Zones latching 11111111 255
How to set Re set Si lence Con fig u ra tion (de fault si lence alarms be fore re set)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 033 followed by 000 for a Reset Silences
and 001 for UK Linking.
How to set Sound/Re sound alarms con fig u ra tion (de fault is sound alarms at any time)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 034 followed by 000 for a Sound Alarms
at any time and 001 for Resound only.
How to set Zone short cir cuit con fig u ra tion (de fault is short cir cuit seen as fault)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 035 data as follows:
Decimal equivalent of eight bit number where a ‘1’ signifies a zone short circuit being seen as a fire and a ‘0’
signifies a zone short circuit being seen as a fault, also the bit 0 corresponds to zone 1 and bit 7 corresponds
to zone 8.
E.g. Requirement eight bit number data
For all Zones - short circuit signifies a fault 00000000 000
Zone 1 - short circuit signifies a fire 00000001 001
Zones 3,5&6 - short circuit signifies a fire 00110100 052
All Zones - short circuit signifies a fire 11111111 255
How to set the num ber of zones used (de fault is 8 zone)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 036 followed by data as follows:
001 for One zone panel, 002 for Two zone panel, 004 for Four zone panel and 008 for Eight zone panel.
How to change Charger Out put level (de fault is 128)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 037 followed by a number between 000
and 255.
How to change the Re set Du ra tion (de fault is 010)
q Enter 4 digit AL4 access code (7426), Press Shift, Enter data 9000 038 followed by a number between 000
and 100, in tenths of a second.
Fault indications Fire Panels
16 4188-424 is sue 6_Part 1_06-12
Fault indications
All fault repairs should be
carried out by the
servicing organisation.
In a fault condition:
· the common Fault light
is lit
· appropriate Fault light
is also lit
· internal Fault Buzzer sounds
intermittent tone
· Multiple faults are
simultaneously annunciated
when this does not cause
confusion.
NOTE: Normally the fault lights
will be automatically extinguished
once the fault condition is
rectified.
NOTE: If the system detects a
fire during a fault condition the
fault indicators may be
extinguished.
How to si lence the fault
buzzer
q Press the 3 digit code, if
re quired and then press Can cel
Buzzer.
q Notice the buzzer is silenced
but visual indications remain
active.
NOTE: The sounder circuits
are pulse monitored for
failure.
Cancel
Buzzer
System
Reset
Sound
Alarms
Silence
Alarms
1
2 3
4
5 6
7
8
9
0
v
Shift or Function
key
Shift
Numeric
keypad
Display test
key
Display
Essential controls
Zones
FIRE
Fault
System
Power
Earth
Sounder
Disabled
Test
Delay
Access /
Function
Normally lit
to indicate
Power supply
healthy
The light is lit when
the Shift/Function key is pressed
or there is an entry to controls
with coded access
ZONE Fire, Fault or Disablement indications
Other Fault
indications
1red
yellow
2 3 4 5 6 7
yellow
yellow
yellow
green
8
Power
yellow
Figure 15 Fault indicators
Faults Cause
What is a Zone
fault?
A zone fault occurs when a zone circuit cable is open
circuit or short circuit, or the end-of-line capacitor unit
has been disconnected or a detector has been
removed.
What is a
Sounder fault?
A sounder fault occurs when a sounder circuit cable
is open circuit or short circuit, or the end-of-line
resistor unit has been disconnected.
What is a Mains
power fault?
A mains failure occurs when the mains power supply
to the panel is removed. This can occur on mains
fuse failure or mains supply disconnection.
What is a Battery
power fault?
A battery supply failure occurs when the battery
supply to the panel has failed (due to aging process)
or battery voltage is too low or is disconnected or the
battery fuse has failed.
What is an Earth
fault?
An earth fault occurs when there is an electrical path
for current flow from the system to earth connections.
What is a Repeat
panel fault?
A Repeat Panel fault occurs when a fault is detected
within the Repeat Panel
What is a Repeat
panel link fault?
A repeat panel link fault occurs when there is a
communication failure between the control and
repeat panels or if the link has been removed or
damaged.
What is a System
Fault?
A system fault occurs in the event that the
microprocessor or software fails.
What is a charger
fault?
A charger fault occurs when the charger will not
switch off or will not provide charge when on.
What is a power
fault?
A power fault occurs when there is an incorrect 24V
level or fuse failure. Also occurs if the sounder output
supply is at the incorrect level or overloaded during
alarm condition.
Table 3 Types of faults
Fault find ing
Fire Panels Fault find ing
4188-424 is sue 6_Part 1_06-12 17
Is the Green
Power Indicator lit steadily
and are all other indicators
extinguished?
Are the fire/zone
fire indicators lit?
Yes
Yes
Is the Test indicator lit?
Yes
Are the Fault
and Power fault indicators lit
or flashing?
Yes
Are the Fault
and Earth Fault indicators lit or
flashing?
Yes
Panel is in normal
operating condition
Refer to Operating
Instructions
Are the Fault
and Sounder Fault
indicators flashing?
Yes
Are the Fault
and Zone Fault indicators
flashing?
Yes
Are the
Fault and Access/
Function indicators
pulsing?
Yes
Are the Fault
and System Fault
indicators On and is the
Power On indicator
O
n
or flashing?
Yes
Are the Zone
Fault and Disabled
indicators lit?
Are the Sounder
Fault and Disabled
indicators lit
Refer to Specialist help
Yes
Yes
Refer to the Test
mode, see Page 11
18
18
Refer to the PSU Fault
Indications table, Page
Refer to the Earth
Fault Indications table,
Page
Refer to the Zone/
Sounder Indications
table, Page
Refer to the Repeat
Panel Faults table, Page
Refer to the System
Fault (Software) table,
Page
Refer to Zone/
Sounder
Indications
table, Page
19
19
19
19
PSU Fault In di ca tions
Earth Fault In di ca tions
Fault find ing Fire Panels
18 4188-424 is sue 6_Part 1_06-12
At Main Panel
Green Power Indicator Power Fault Indicator Meaning
Steady Off No PSU Faults
Slow Flash Slow Flash Mains failed (Common Fault indicator also flashes to save batteries*)
Slow Flash Fast Flash Battery disconnected/Battery fault or Charger fault
Slow Flash Steady Auxiliary supply/sounder output supply fault
* If Access/Function indicator flashes slowly, there is either a comms fault, an earth fault or a PSU fault on the Repeat Panel.
At Repeat Panel
Green Power Indicator Power Fault Indicator Meaning
Steady Off No PSU Fault in either Main Panel or Repeat panel
Steady Slow Flash Mains failed at Main Panel
Steady Fast Flash Battery disconnected/Battery fault/Charger fault at Main Panel
Steady Steady Auxiliary supply/sounder output supply fault at Main Panel
Slow Flash Slow Flash Mains failed at Repeat Panel
Slow Flash Fast Flash Battery disconnected/Battery fault/Charger fault at Repeat Panel
* If Access/Function indicator flashes slowly, there is a comms fault, between the Main Panel and the Repeat Panel.
NOTE: If there is a PSU fault at the Main Panel and the Repeat Panel, then priority is given to the fault at the
Main Panel
At Main panel
Fault -
Yellow
Earth -
Yellow
Power -
Green
Buzzer Auxiliary relay contacts
normally de-energised
Common fault -
normally active
Common fire -
normally deactive
Earth fault
indications
Steady Pulse
Slowly
On Pulse
Slowly
Normal Deactive Deactive
NOTE: If a Repeat panel is connected, the ACCESS/FUNCTION lamp will pulse slowly as well.
At Repeat Panel
Earth Fault Indicator
Off No earth fault at the Repeat Panel or the Main Panel
Steady Indication Earth fault local to the Main Panel
Fire Panels Fault find ing
4188-424 is sue 6_Part 1_06-12 19
Zone/Sounder Indications
Re peat Panel Fault In di ca tions
Sys tem Fault (Soft ware) In di ca tions
Visual Indications Audible
Indications
Signals out
Condition Zone
Fault
(1-8) -
Yellow
Fault -
Yellow
Sounder
- Yellow
Disabled
- Yellow
Power -
Green
Buzzer Aux Relay
contacts
Normally
de-
energised
Common fault -
Normally active
Common
fire-
Normally
deactive
Zone
fault
Pulse
slowly
Steady On Pulse slowly Normal Deactive Deactive
Sounder
fault
Steady Pulse
slowly
On Pulse slowly Normal Deactive Deactive
Disable
zone
On On On Normal Active Deactive
Disable
Sounder
On On On Normal Active Deactive
Visual indications Audible
indication
Signals out
Condition Fault -
Yellow
Power -
Green
Access/
Function -
Yellow
Buzzer Aux Relay contacts
Normally de-energised
Common fault -
Normally active
Common fire-
Normally deactive
Repeat
Panel Link
Fault
Steady On Pulse
slowly
Pulse
slowly
Normal Deactive Deactive
Visual indications Audible
indication
Signals out
Condition Fault -
Yellow
System -
Yellow
Power -
Green
Buzzer Aux Relay contacts
Normally de-energised
Common fault -
Normally active
Common fire-
Normally deactive
Software
system
fault
On On On (Pulses
at Repeat
panel)
On Normal Deactive Deactive
Note: Batteries are not supplied with some panels
Number of Zone (detection) circuits 1 - Zone panel 2 - Zone panel 4 - Zone panel 8 - Zone panel
Zone circuit voltage range
19V to 25.5V
Zone circuit load (maximum)
Maximum Quiescent current: 3.0mA per zone OR
EN54 compliance limitation: 32 devices OR
Maximum of 20 diode bases per zone
(Short circuit current limited to < 20mA)
Number of Sounder circuits
2 2 4 8
Sounder circuit (shared load)
0.5A per output, 1A max shared load
@ 24V +2V -2V with mains present
(24V +2V -4V battery only)
Sounder circuit fuse
0.75A resettable
End-of-line unit
Zone circuit: Capacitor (diode) unit Sounder circuit: 10K ohms resistor
OR Biploar Capacitor
Flush fixing kit 13270-29 (Cut out required 378mm wide x 245mm high x 60mm deep)
Colour
Front cover - Grey RAL 7000 (standard)
Assembled panel size (in mm)
395 wide x 274 high x 87 deep
Weight (with batteries) approximate
5.8kg 5.8kg 5.8kg 6.2kg
Operating temperature and humidity
0 - 40
o
C low to +95% RH non condensing
Storage temperature and humidity
-5
o
C to +50
o
C low to +95% RH condensing
Standards
EN54-2: 1997, A1:2006 plus EN54-4: 1997, A1:2002, A2:2006
Approvals
BSI approval acquired
Emission
BS EN50081-1:1992: Part 1 Residential, Commercial & Light industry
Class B limits
Immunity
BS EN50130-4: 1996: Part 4 Alarm systems : Electromagnetic compatibility
Product family standard: Immunity requirements for components of fire, intruder
and social alarm systems
IP rating (BS5490)
IP31 (indoor)
Knock-In cable entry points
13 - top & 13 - back
Terminal size
2.5mm
2
maximum
Battery standby with 1mA load per
zone and 1A total sounder alarm load
72hr standby plus 0.5hr with alarm load
Auxiliary contacts
(operates with fire)
Pair of normally closed (NC) and a pair of normally open (NO) contacts rated
1A @ 24V dc resistive load (Maximum 100m cable distance)
Common Fault
Open collector - normally On (35mA limit)
Common Fire
Open collector - normally Off (16mA limit)
Class change
Normally open push button, up to 100m cable distance away from the panel
24V Power supply (Monitored) 250mA maximum at 24V dc +2V, -4V 500mA maximum at 24V dc +1.5V, -4V
User access: By means of code entry
via numeric key pad
(AL1 Authorised user - No code is
required)
AL2 Site security 3 digit code - 123
AL3 Site engineering 3 digit code - 321
AL4 Engineers 4 digit code - 7426
Reset AL2 & AL3 codes 4 digit code - 2623
Key pad button controls Sound alarm, Silence alarm, System Reset & Cancel buzzer & numeric keypad.
Buzzer for local audible indications Fire & System Fault - continuous sound Fault - intermittent sound
(via piezoelectric buzzer operating at 2 or 2.5KHz 70dB(A) at 1m)
Visual indications
FIRE & ZONES-fire (Red LEDs ‘lights’)
ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, Test, Power,
Access/Function (Yellow LEDs ‘lights’)
Power on (Green LED ‘lights’)
Delay ( Yellow LED ‘lights’)
Repeat panel connections via serial port, see also repeat panel specification
Specification for the Control panel Fire Panels
20 4188-424 is sue 6_Part 1_06-12
Specification for the Control panel
Fire Panels Specification for the Control panel
4188-424 is sue 6_Part 1_06-12 21
Spec i fi ca tion for con trol panel’s Power sup ply
The control panel consists of single board containing both the control and indicating equipment and the power
supply. A 50VA mains transformer provides a low voltage (30Vac) supply into the power supply circuits. The on
board power supply circuits produce a regulated 24V dc supply, a 24V sounder supply and a battery charger
output.
Note the control and monitoring of the power supply unit is under direct control of the microprocessor of the
control and indicating equipment.
Mains supply
Mains
230V AC +10% -15% 50Hz
Fused at 3.15A Ceramic Time delay
Typical standby power 6W
Maximum alarm power <60W (8 zone panel)
Internal supply
24V supply (Feeds current limited
zone circuit & 24V fused output)
24V dc +2V -2V (or 24V +2V -4V battery operation)
current limited
<5% ripple voltage
24V Sounder supply (Feeds fused
sounder circuit)
24V dc +2V -2V (24V +2V -4V battery operation)
Current limited
<5% ripple voltage
Battery Charger Float voltage 27.3V +1% -1% @ 20degC
Compensation -36mV/K (nominal)
Current limited @ 400mA +20% -20%
Fused @ 3.15A Ceramic Time delay
Reverse protection
Use the Battery Standby Calculator sheet available from 'www.gentexpert.co.uk' to determine the site specific battery
standby capability of the system.
Battery supply
Approved Batteries 12V, 2.1Ah POWERSONIC
12V 3.4Ah POWERSONIC
Type and capacity Sealed lead acid (value regulated)
2x12V, 2.1Ah min to 3.4Ah* max (1,2&4 zone panels)
2x12V, 3.4Ah*max (8 zone panel)
* max capacity limited by internal panel size
Maximum current 1.6A (no mains present)
Final voltage 21.6V
Installation requirements As per control panel
EN54 Part 4 data I min -> 120uA
I maxa -> 21.6mA
I maxb -> 1.5A
Ri max-> 2W
UVLO -> 18.5V ± 1.5V
Specification for the Repeat panel Fire Panels
22 4188-424 is sue 6_Part 1_06-12
Specification for the Repeat panel
Number of Zones
8 - Zone (standard size)
Colour
Front cover - Grey RAL 7000
Assembled panel size (in mm)
395 wide x 274 high x 87 deep
Weight (with batteries) approximate
5.8kg (2.1Ah battery) / 6.2Kg (with 3.4Ah battery)
Operating temperature and humidity
0 - 40
o
C low to +95% RH non condensing
Storage temperature and humidity
-5
o
C to +50
o
C low to +95% RH condensing
Approvals
Not applicable
Emission
BS EN50081-1:1992: Part 1 Residential, Commercial & Light industry
Class B limits
Immunity
BS EN50130-4: 1996: Part 4 Alarm systems : Electromagnetic compatibility
Product family standard: Immunity requirements for components of fire,
intruder and social alarm systems
IP rating (BS5490)
IP31 (indoor)
Flush fixing kit
13270-29 (Cut out required 378mm wide x 245mm high x 60mm deep)
Mains operating voltage
230V ac +10% -15% 50Hz
Knock-In cable entry points
Top & back entries
Terminal size
2.5mm
2
maximum
Battery supply (sealed lead acid)
2-off12V 2.1Ah - 3.4Ah (See applicable batteries as listed for Control panel
Standby duration
72hr standby
User access: By means of code entry
via numeric key pad
(AL1 Authorised user - No code is
required)
AL2 Site security 3 digit code - 123
AL3 Site engineering 3 digit code - 321
AL4 Engineers 4 digit code - 7426
Reset AL2 & AL3 codes 4 digit code - 2623
NOTE: Only a limited number of functions are accessible at the repeat panel.
Key pad button controls Sound alarm, Silence alarm, System Reset & Cancel buzzer & numeric
keypad.
Buzzer for local audible indications Fire & System Fault - continuous sound Fault - intermittent sound
(via piezoelectric buzzer operating at 2 or 2.5KHz 70dB(A) at 1m)
Visual indications
FIRE & ZONES-fire (Red LEDs ‘lights’)
ZONES-fault, Fault, System, Power, Earth, Sounder, Disable, Test, Power,
Access/Function (Yellow LEDs ‘lights’)
Power on (Green LED ‘lights’)
Delay (LED ‘lights’)
Repeat panel (standard 8 zone)
A maximum of 1 repeat panel can be connected in series with the control
panel
Repeat panel connections
via serial port
Fire Panels Parts list
4188-424 is sue 6_Part 1_06-12 23
Parts list
Panels
Part number Description
# - less batteries
13270-02LB 2 Zone control panel #
75585-02NMB 2 Zone control panel #
13270-04LB 4 Zone control panel #
75585-04NMB 4 Zone control panel #
13270-08LB 8 Zone control panel #
75585-08NMB 8 Zone control panel #
13271-08LB Repeat panel #
75586-08NMB Repeat panel #
13270-29 Panel flush fixing kit
Au to matic Fire De tec tors
Part number Description
178xx range
17840-01 Optical Smoke Detector
17850-01 Fixed Temperature (58
o
C) Heat
17860-01 Rate of Rise Heat Detector
17870-01 High Temperature Detector
17800-01 Base (without diode)
17801-01 Base (with diode)
17800-02 Low profile base (without diode)
17801-02 Low profile base (with diode)
07011-40 Optical Beam reflective
` 50m to 100m
NOTE: The beam detector should be powered from
an external 24V power supply. This arrangement
requires a reset switch in series with the supply.
Vision range
Part number Description
2020P Optical Smoke detector
2020PT Optical Heat detector
2020F Fixed Temp Heat detector
2020HF High Temp Heat detector
2020R Rate of Rise Heat Detector
2020B Standard Detector Base
2020BSD Standard Det. Base with diode
2020DB Deep Detector Base
2020DBSB Deep Detector Base with diode
72499-24NM Circular remote LED
ZF18 Square remote LED
17899-44 Repeat Relay
Man ual call points (MCP)
Part number Description
XENS-850 or Flush MCP 470 Ohms Glass
MCP1A-R470FG-01
XENS-805 or Surface MCP 470 Ohms Re-settable
MCP1A-R470SF-01
XENS-829 or Weatherproof MCP 470 Ohms resistor
MWCP1A-R470SG-01 Glass
XENS-807 Key Operated, Surface Mounted c/w
backbox
XENS-891 Spare Glasses for MCP XENS-800
(Pack of 10)
XENS-890 Resettable element for XENS-800
and XENS-805 (pack of 10)
XENS-892 Hinged protective cover for use on
XENS-800 range (pack of 10)
XENS-895 Surface Backbox for XENS-800 range
of MCP (pack of 10)
XENS-893 Replacement keys for XENS-807
K/S MCP (pack of 10)
XENS-899 Pack of test keys (pack of 10)
71150-62NM MCP red surface mounted for
NO and NC connections
24Vdc Alarm sig nals
Part number Description
12141-04 Electronic bell (red) IP40
02601-31 Squashni Sounder 24Vdc 18mA
IP54 93dBA @ 1m
02519-52 Bedhead Sounder 24Vdc 18mA
(white) 97dBA @ 1m
C3IP-SN-R IP65 Electronic Sounder
Red (100dBA)
C3IP-SN-W IP65 Electronic Sounder
White (100dBA)
C3-SN-R IP31 Electronic Sounder
Red (100dBA)
C3-SN-W IP31 Electronic Sounder
White (100dBA)
C3IP-SN-ST-RR IP65 Electronic Sounder/Strobe
Red (100dBA)
C3IP-SN-ST-WR IP65 Electronic Sounder/Strobe
White (100dBA)
C3-SN-ST-RR IP31Electronic Sounder/Strobe
Red (100dBA)
C3-SN-ST-WR IP31 Electronic Sounder/Strobe
White (100dBA)
C3-VP-ST-RR IP31Voice sounder/Strobe
Red (100dBA)
C3-VP-ST-WR IP31 Voice sounder/Strobe
White (100dBA)
C2IP-ST-RR IP65 Ultra Low current Strobe
(5mA) red body/red lens
by Honeywell
0086
Gent by Honeywell
Hamilton Industrial Park, 140 Waterside Road, Leicester LE5 1TN, UK
0086-CPD-553764
Xenex
EN54-2: 1997, A1:2006
Control and Indicating equipment for fire detection and fire alarm systems
in buildings
7.8 Output to Fire alarm device(s)
7.10 Test Conditions
7.11 Delays to action outputs
EN54-4: 1997, A1:2002, A2:2006
Power supply equipment for fire detection and fire alarm systems in
buildings.
Other technical data: see documents in project file 6304, held by the
manufacturer.
At the end of their useful life, the packaging,
product and batteries should be disposed of
via a suitable recycling centre and in
accordance with national or local legislation.
Do not dispose of with your normal household waste.
Do not burn.
WEEE Directive:
At the end of their useful life, the packaging,
product and batteries should be
disposed of via a suitable recycling centre.
24Vdc Alarm sig nals
Part number Description
CONV-IP-SN-R IP55 Electronic Sounder
Red 100 dBA
CONV-SN-R IP31 Electronic Sounder
Red 100dBA
CONV-SN-ST-RR IP55 Electronic Sounder Strobe
Red body Red lens 100 dBA
CONV-IP-ST-RR IP55 Ultra low current Strobe
Red body Red lens
CONV-IP-VP-R IP55 Voice Enhanced Electronic
Sounder Red (100 dBA)
CONV-IP-VP-ST-RR IP55 Voice Enhanced
Electronic Sounder and Strobe
Red Body Red Lens (100 dBA)
74451-24NM Multitone Low Profile Sounder,
Red with shallow base
74452-24NM Multitone Low Profile Sounder,
Red with deep base
74456-24NM Sounder base, White 3 tone
74455-24NM Bedhead Sounder
74456-61NM Sounder base cover plate
74430-88NM 6" Electronic bell 24V dc
Red IP40
74432-88NM 6" Electronic bell, weather
resistant Electronic bell,
24V dc Red IP55
Panel Ac ces so ries
Part num ber De scrip tion
XENS-BATT-12 2 x 12V 2.1Ah bat tery
(for 1, 2 & 4 zone
panel plus re peat panel)
XENS-BATT-48 2 x 12V 3.4Ah bat tery
(for 8 zone panel)
XEN-FFR Fire fault relay unit
Parts list Fire pan els
Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the
content hereof without obligation to notify any person of such revisions of changes.
Hamilton Industrial Park, Waterside Road, Leicester LE5 1TN, UK Website: www.gent.co.uk
Telephone: +44 (0) 116 246 2000 Tech. Support: www.gentexpert.co.uk Fax (UK): +44 (0)116 246 2300
4188-424 issue 6_Part 1_06-12