Technical data
Type Order No.
Pcs.
Pkt.
Fuse terminal block
1
),
for mounting on
3
,
for cartridge fuse inserts 6 x 32 mm, with
light indicator for:
15 - 30 V AC/DC, 1 - 2.5 mA terminal width 8.2
110 - 250 V AC/DC, 0.5 - 2.5 mA terminal width 8.2
ST 4-HESILED 24 (6,3 x 32) 30 38 76 5 50
ST 4-HESILA 250 (6,3 x 32) 30 38 77 8 50
(1)
Plug-in bridge,
for 2-pos.
cross-connections in the 3-pos.
terminal center 4-pos.
5-pos.
10-pos.
FBS 2-8
I
max
.
: 32 A
30 30 28 4 10
FBS 3-8
32 A
30 30 29 7 10
FBS 4-8
32 A
30 30 30 7 10
FBS 5-8
32 A
30 30 31 0 10
FBS 10-8
32 A
30 30 32 3 10
(2)
Partition plate,
for
visual and electrical separation
of terminal groups, 2 mm thick
ATP-QTC TWIN 32 06 21 2 50
(3)
Adapter bridge,
for connecting an
ST 4-HESI (6,3 x 32) to an ST 4, ST 2,5 or QTC 1,5
RB ST 6-(2,5/4) 30 30 86 0 50
(4)
Screwdriver,
for
actuating the tension spring
SZF 1 - 0,6 x 3,5 12 04 51 7 10
(5)
Zack strip,
flat, for labeling the
center and outer marker grooves white
ZBF 8:UNPRINTED 08 08 78 1 10
(6)
Zack strip,
10-section, for
labeling on the white
fuse lever
ZB 6:UNPRINTED 10 51 00 3 10
Dimensions
Width / length [mm] 8.2 / 76.5
Height (NS 35/7,5 / NS 35/15) [mm] 69 / 76.5
Technical data in accordance with IEC/ DIN VDE
Fuse type ISO/DIS 8820/DIN 72 581-3 / dimensions – / [mm] G / 6 x 32
Maximum current with single arrangement [A] 10
Max. power dissipation
at 23 °C based on E DIN VDE 0611-6: 2001-04 [W] see table
Rated surge voltage / contamination class [kV] / – 6 / 3
Surge voltage category / insulation material group – / – III / I
Connection capacity
Stranded with ferrule with plastic sleeve [mm
2
] 0.25 - 4
Stranded with ferrule without plastic sleeve [mm
2
] 0.25 - 4
Stranded with TWIN ferrule with plastic sleeve [mm
2
] 0.5 - 1
Stripping length [mm] 10
Internal cylindrical gauge (IEC 60 947-1) A 4
Insulating material PA
Inflammability class in acc. with UL 94 V0
Approval data (UL and CSA/CUL)
Nominal voltage / current / conductor sizes UL: [V] / [A] / AWG applied for 600 / 10 / 24-10
CSA/CUL: [V] / [A] / AWG applied for 600 / 10 / 24-10
Spring Cage Fuse Terminal Block
ST 4-HESILED and
ST 4-HESILA (6,3 x 32)
Phoenix Contact page 5 of 7
(IEC) rigid flexible I U
[mm
2
] solid stranded AWG [A] [V]
IEC 60 947-7-3 0.08-6 0.08-4 28-10 10* 400*
*Current and voltage are determined by the fuse used.
1
) If the fuse is defective, the downstream circuit is not off load.
Max. power dissipation at 23°C (based on E DIN VDE 0611-6:2001-04)
When selecting cartridge fuse inserts, please ensure that the maximum power dissipation specified below is not exceeded. Details
can be obtained from the fuse suppliers.
Te rminal block type U Overload protection Short-circuit protection only I
max.
[V] Single Interconnected Single Interconnected [A]
ST 4-HESI (6,3 x 32) 400 1.6 W 1.6 W 4.0 W 2.5 W 10
Cartridge fuse terminal blocks based on
E DIN VDE 0611-6: 2001-04